Appendix 1 Details of Remote I/O Signals
Appendix 1.1 Remote input signals
APPENDICES
Appendix 1 Details of Remote I/O Signals
This section describes the details of remote I/O signals assigned to the master/local module.
The described assignment of device numbers assumes that the remote I/O signals of A/D converter modules are
assigned as follows:
Appendix 1.1 Remote input signals
(1) Warning flag
At the occurrence of a minor error, Warning flag (RX7) turns on.
Eliminating the cause of the minor error occurred and waiting for five seconds results in Latest warning code
(RWr1) turning to 0000H and Warning flag (RX7) turning off.
(a) Device number
The device number of this input signal is as follows:
Signal name Main A/D converter module Extension A/D converter module
Remote input signals RX0 to RX1F RX20 to RX2F
Remote output signals RY0 to RY1F RY20 to RY2F
Signal name Main A/D converter module Extension A/D converter module
Warning flag RX7
Warning flag (RX7)
Latest warning code (RWr1)
Minor error
removed
OFF
ON
ON
OFF
0000HError code
Controlled by the A/D converter module
Minor error
occurred
Remote READY (RXB)
0000H
5 seconds elapsed
5 seconds