EasyManua.ls Logo

Mitsubishi Electric QX10 - User Manual

Mitsubishi Electric QX10
158 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
I/O Module Type Building Block
User's Manual
QX10 QY10
QX10-TS QY10-TS
QX28 QY18A
QX40 QY22
QX40-S1 QY40P
QX40-TS QY40P-TS
QX40H QY41H
QX41 QY41P
QX41-S1 QY42P
QX41-S2 QY50
QX42 QY68A
QX42-S1 QY70
QX50 QY71
QX70 QY80
QX70H QY80-TS
QX71 QY81P
QX72 QY82P
QX80 QH42P
QX80-TS QX41Y41P
QX80H QX48Y57
QX81 QI60
QX81-S2
QX82
QX82-S1
QX90H

Table of Contents

Questions and Answers

  • C
    Christine FrankAug 16, 2025
    What to do if an input signal does not turn off on my Mitsubishi Electric QX10?
    • A
      Anthony DavisAug 16, 2025
      If an input signal on your Mitsubishi Electric Controller doesn't turn off, it could be due to a few reasons. One cause may be leakage current from the input switch. To resolve this, connect an appropriate resistor to ensure the voltage across the input module terminals is less than the off voltage. A CR constant of 0.1 to 0.47 F + 47 to 120? (1/2W) is recommended. Another cause could be driving the system with a limit switch that has a neon lamp. The solution is the same as above, or you could create an independent display circuit. Lastly, leakage current from the wiring cable's line capacity could be the problem. The solution is the same as the first example; however, leakage current is not generated when the power supply is located in the input equipment side.
  • R
    Rachel GomezOct 31, 2025
    What to do if Mitsubishi Electric QX10 Controller input signal does not turn OFF?
    • M
      Madison RushOct 31, 2025
      If the input signal of your Mitsubishi Electric Controller doesn't turn OFF, several factors could be the cause. Here are some potential solutions: * If the issue is due to leakage current from the input switch, connect an appropriate resistor to lower the voltage across the input module terminals below the OFF voltage value. A CR constant of 0.1 to 47 F + 47 to 120 (1/2W) is recommended. * If it's due to a limit switch with a neon lamp, apply the same solution as above or create an independent display circuit. * For leakage current from the wiring cable's line capacity, use the same resistor solution. Note that leakage current isn't generated when the power supply is on the input equipment side. * If using a switch with an LED indicator, connect a resistor to lower the voltage be...

Summary

SAFETY PRECAUTIONS

Design Precautions

Configuration and operational safety measures to prevent accidents.

Installation Precautions

Wiring Precautions

Startup and Maintenance Precautions

GENERAL SPECIFICATIONS AND PRECAUTIONS FOR USE

Precautions for Use

Covers essential safety precautions for using various types of I/O modules.

Input module Precautions

Specific safety advice for using DC input modules and high-speed input modules.

INPUT MODULE SPECIFICATIONS

QX10 AC Input Module

Specifications and external connection details for the QX10 AC input module.

QX40 DC Input Module (Positive Common Type)

Specifications and external connection for the QX40 DC input module (positive common type).

QX40 H DC High-Speed Input Module (Positive Common Type)

Specifications and external connection for the QX40H DC high-speed input module (positive common type).

OUTPUT MODULE SPECIFICATIONS

Various Settings for I;O Module

Setting of error-time output mode

Switch setting of interrupt module

I;O COMBINED MODULE

INTERRUPT MODULE

CONNECTORS

SPECIFICATIONS OF CONNECTOR;TERMINAL BLOCK CONVERTER MODULES

SPRING CLAMP TERMINAL BLOCK

I;O MODULE TROUBLESHOOTING

Input Circuit Troubleshooting

Describes common problems with input circuits and their corrective actions.

Output Circuit Troubleshooting

Describes common problems with output circuits and their corrective actions.

WARRANTY

Mitsubishi Electric QX10 Specifications

General IconGeneral
Input Voltage24 VDC
IsolationPhotocoupler isolation
MountingDIN rail
Number of Input Points16 points
Applicable PLCMitsubishi Electric Q Series
Connection TypeTerminal block
Operating Temperature0 to 55 degree C
Storage Temperature-25 to 75 °C