EasyManuals Logo

Mitsubishi Heavy Industries FDT100VNAWVH User Manual

Mitsubishi Heavy Industries FDT100VNAWVH
204 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #111 background imageLoading...
Page #111 background image
'19 • PAC-SM-309
-
110
-
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content
E19
Indoor unit operation check,
drain pump motor check setting error
Keeps ashing
1-time ash
Keeps ashing
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Is SW7-1
on the indoor unit control
PCB ON ?
E19 occurs
when the power ON
NO
YES
Defective indoor unit
control PCB (Defective
SW7)
Replace.
Turn SW7-1 on the indoor
unit control PCB OFF and
reset the power.
2. Error detection method
After indoor operation check,
when the communication
between indoor and outdoor
unit is established and SW7-1 is
still kept ON.
3 .
Condition of error displayed
Same as above
4. Presumable cause
Mistake in SW7-1 setting
(Due to forgetting to turn OFF
SW7-1 after indoor operation
check)
Note: