'19 • PAC-SM-309
-
95
-
WAIT
Communication error at
initial operation (1/3)
Keepsashing
Keepsashing
Stays OFF
2-timeash
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
NO
NO
NO
“ ” is still displayed on the
remote control LED 2 minutes
after power ON.
YES
NO
NO
Is the outdoor
unit control green LED
flashing?
YES
YES
YES
YES
Is the indoor
unit green LED flashing?
Is the outdoor unit
control red LED flashing
twice?
Are wires
connected properly between indoor/
outdoor units?
YES
YES
NO
Is approx.
DC20V detected between - on
the outdoor unit terminal
block?
Is approx.
DC20V detected between - on
the indoor unit terminal
block?
WA IT
To next page
Defective indoor unit control
PCB
Replace.
Defective indoor unit control
PCB
Replace.
Defective remote control
Replace.
Broken remote control wire
Y
Replace.
Correct connection wires
between indoor and
outdoor units.
Defective outdoor unit main
PCB
Replace.
Defective connection wire
(Broken)
Noise
Defective indoor unit control
or power PCB
Replace.
2. Error detection method
3 .
Condition of error displayed
4. Presumable cause
Faulty indoor unit control or
power PCB
Defective remote control
Broken remote control wire
Faulty outdoor unit main PCB
Broken connection wires
Note:
Error code
Remote control:
LED Green Red
Indoor
Outdoor
Content

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Heavy Industries FDT100VNAWVH and is the answer not in the manual?

Mitsubishi Heavy Industries FDT100VNAWVH Specifications

General IconGeneral
BrandMitsubishi Heavy Industries
ModelFDT100VNAWVH
CategoryAir Conditioner
LanguageEnglish

Related product manuals