EasyManua.ls Logo

Mitsubishi A1SD75M3

Mitsubishi A1SD75M3
746 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14 - 19
MELSEC-A
14 TROUBLESHOOTING
Relevant buffer memory address
Axis 1 Axis 2 Axis 3
Setting range
(Setting given in sequence program)
Remedy
6
7
156
157
306
307
1 to 1000000 [pulse/s]
1 to 600000000 [mm/min, etc.]
8
9
158
159
308
309
(One-word type) 1 to 65535
(Two-word type) 1 to 8388608
10
11
160
161
310
311
(One-word type) 1 to 65535
(Two-word type) 1 to 8388608
12
13
162
163
312
313
1 to 1000000 [pulse/s]
1 to 600000000 [mm/min, etc.]
Change the setting to within the setting range and turn
OFF then ON the PLC READY signal (Y1D).
16
17
166
167
316
317
[mm] [inch] [pulse]
-2147483648 to 2147483647
[degree] 0 to 35999999
Change the setting to within the setting range.
In case of a unit other than “degree,” change the settings
so that the lower limit value is smaller than the upper limit
value.
When the absolute position restoration mode is the
"infinite length mode", make the software stroke limit
function invalid.
(Refer to section 12.4.3, section 12.6.2.)
18
19
168
169
318
319
[mm] [inch] [pulse]
-2147483648 to 2147483647
[degree] 0 to 35999999
Change the setting to within the setting range.
Change the settings so that the lower limit value is
smaller than the upper limit value with a unit other than
“degree.”
When the absolute position restoration mode is the
"infinite length mode", make the software stroke limit
function invalid.
(Refer to section 12.4.3, section 12.6.2.)
20 170 320 0, 1
21 171 321 0, 1
22
23
172
173
322
323
[mm] [inch] [pulse]
1 to 32767000
[degree] 1 to 32767
24 174 324 1 to 500
25 175 325 0, 1
Change the setting to within the setting range and turn
OFF then ON the PLC READY signal (Y1D).

Related product manuals