12
WT09050X01
4. Specifications
(1) M models
Model PURY-M200YNW-A1
*3
PURY-M250YNW-A1
*3
PURY-M300YNW-A1
*3
PURY-M350YNW-A1
*3
Sound pressure level
*4
(50/60 Hz) 59 dB <A> 60.5 dB <A> 61 dB <A> 62.5 dB <A>
External static pressure 0 Pa
*2
Indoor unit
Total capacity 50% to 150%
*1
Model 10 to 125
Quantity 1 to 30 1 to 37 2 to 45 2 to 50
Operation
temperature
(Cooling)
Indoor W.B. +15.0°C to +24.0°C (+59.0°F to +75.0°F)
Outdoor D.B. -5.0°C to +52.0°C (+23.0°F to +125.6°F)
Operation
temperature
(Heating)
Indoor D.B. +15.0°C to +27.0°C (+59.0°F to +81.0°F)
Outdoor W.B. -20.0°C to +15.5°C (-4.0°F to +60.0°F)
Model PURY-M400YNW-A1
*3
PURY-M450YNW-A1
*3
PURY-M500YNW-A1
*3
Sound pressure level
*4
(50/60 Hz) 65 dB <A> 65.5 dB <A> 63.5 dB <A>
External static pressure 0 Pa
*2
Indoor unit
Total capacity 50% to 150%
*1
Model 10 to 125
Quantity 2 to 50 2 to 50 2 to 50
Operation
temperature
(Cooling)
Indoor W.B. +15.0°C to +24.0°C (+59.0°F to +75.0°F)
Outdoor D.B. -5.0°C to +52.0°C (+23.0°F to +125.6°F)
Operation
temperature
(Heating)
Indoor D.B. +15.0°C to +27.0°C (+59.0°F to +81.0°F)
Outdoor W.B. -20.0°C to +15.5°C (-4.0°F to +60.0°F)
*1 The maximum total capacity of indoor units operating simultaneously is 150%.
*2 To enable the high static pressure setting, set the dipswitch on the main board as follows.
SW6-5: ON SW6-5: OFF
SW6-4: ON 80 Pa 60 Pa
SW6-4: OFF 30 Pa 0 Pa
*3 These models can be used for a Hybrid City Multi system.
*4 Cooling mode
(2) EM models
Model PURY-EM200YNW-A1
*3
PURY-EM250YNW-A1
*3
PURY-EM300YNW-A1
*3
PURY-EM350YNW-A1
*3
Sound pressure level
*4
(50/60 Hz) 59 dB <A> 60.5 dB <A> 61 dB <A> 62.5 dB <A>
External static pressure 0 Pa
*2
Indoor unit
Total capacity 50% to 150%
*1
Model 10 to 125
Quantity 1 to 30 1 to 37 2 to 45 2 to 50
Operation
temperature
(Cooling)
Indoor W.B. +15.0°C to +24.0°C (+59.0°F to +75.0°F)
Outdoor D.B. -5.0°C to +52.0°C (+23.0°F to +125.6°F)
Operation
temperature
(Heating)
Indoor D.B. +15.0°C to +27.0°C (+59.0°F to +81.0°F)
Outdoor W.B. -20.0°C to +15.5°C (-4.0°F to +60.0°F)
Model PURY-EM400YNW-A1
*3
PURY-EM450YNW-A1
*3
PURY-EM500YNW-A1
*3
Sound pressure level
*4
(50/60 Hz) 65 dB <A> 65.5 dB <A> 63.5 dB <A>
External static pressure 0 Pa
*2
Indoor unit
Total capacity 50% to 150%
*1
Model 10 to 125
Quantity 2 to 50 2 to 50 2 to 50
Operation
temperature
(Cooling)
Indoor W.B. +15.0°C to +24.0°C (+59.0°F to +75.0°F)
Outdoor D.B. -5.0°C to +52.0°C (+23.0°F to +125.6°F)
Operation
temperature
(Heating)
Indoor D.B. +15.0°C to +27.0°C (+59.0°F to +81.0°F)
Outdoor W.B. -20.0°C to +15.5°C (-4.0°F to +60.0°F)
*1 The maximum total capacity of indoor units operating simultaneously is 150%.
*2 To enable the high static pressure setting, set the dipswitch on the main board as follows.
SW6-5: ON SW6-5: OFF
SW6-4: ON 80 Pa 60 Pa
SW6-4: OFF 30 Pa 0 Pa
*3 These models can be used for a Hybrid City Multi system.
*4 Cooling mode