en
19
WT09050X01
(3) Combination of face-to-face and side-by-side installations
When there are walls in the front and rear of the block of units
h2
h2’
L2’
L4
L2
Ⓐ
Ⓐ
Required minimum distance [mm (in)]
L2 (Rear) L2' (Rear) L4 (Between)
300 (11-13/16) + h2 300 (11-13/16) + h2' 900 (35-7/16)
When there are two walls in an L-shape
h2
L2
L4
L3
Ⓐ
Ⓐ
h3
Required minimum distance [mm (in)]
L2 (Rear) L3 (Right/Left) L4 (Between)
300 (11-13/16) + h2 1000 (39-3/8) + h3 900 (35-7/16)
Ⓐ Leave open in two directions.
Unit height
Unit height
Unit height
Unit height