<A>, <B> Main HBC controller (Total capacity of indoor units: WP375 or below)
<C> Sub HBC controller (Total capacity of indoor units <B> + <C>: WP375 or below)
Outdoor unit
Indoor unit
Main HBC controller
Sub HBC controller
2-Branch Joint Pipe (not supplied)
Joint Pipe Kit (not supplied)
Max. 3 sets for 1 port (Total capacity ≤ WP80)
Item Piping portion Allowable value
Pipe length
Between outdoor unit and HBC controller (refrigerant pipework) A
1 + A 2 + A 3 110 m (360 ft) or below
Water pipework between indoor units and HBC controller f + g 60 m (196 ft) or below
Between HBC controllers B 40 m (131 ft) or below
Difference of
elevation
Between HBC controller and outdoor
units
Outdoor unit above HBC
controller
H 50 m (164 ft) or below
Outdoor unit below HBC
controller
H' 40 m (131 ft) or below
Between indoor units and HBC controller h
1
15 m (10 m
*1
)
(49 ft (32 ft
*1
)) or below
Between indoor units h
2
15 m (10 m
*1
)
(49 ft (32 ft
*1
)) or below
Between HBC controllers h
3
15 m (10 m
*1
)
(49 ft (32 ft
*1
)) or below
*1 The values marked with *1 indicate the values when the total indoor unit capacity exceeds 130% of outdoor unit capacity.
((E)M300)
(WP100, WP125)
(WP10-WP80)
CMB-WM108V-AA + CMB-WM108V-AB
(CMB-WM1016V-AA) (CMB-WM1016V-AB)