Make sure that the pipe connections all the way from the indoor unit are properly insulated.
9-7-2. Insulation for the section of the pipe that goes through a wall
(1) Inner wall (concealed) (2) Outer wall (3) Outer wall (exposed)
(4) Floor (waterproof) (5) Rooftop pipe shaft (6) Protecting the penetrating parts in a fire limit zone
or through a parting wall
1000
(39-3/8)
1000
(39-3/8)
Sleeve
Insulation material
Lagging
Caulking material
Band
Waterproof layer
Sleeve with a flange
Caulk with a nonflammable material such as mortar.
Nonflammable insulation material
When caulking the gaps with mortar, cover the section of the pipe that goes through the wall with a metal sheet to
prevent the insulation material from sagging. For this section, use nonflammable insulation and covering materials.
(Vinyl tape should not be used.)
[mm (in)]