42
WT09050X01
Wiring example
Earth leakage breaker
Local switch (Overcurrent breaker and earth
leakage breaker)
Contactor *
4
Outdoor unit
Pull box
Indoor unit
Earth
Main HBC controller
Sub HBC controller
Be sure to use the appropriate type of overcurrent breaker. Note that generated overcurrent may include some
amount of direct current.
Select the type of breaker for an inverter circuit as an earth leakage breaker. (Mitsubishi Electric NV-S series or its
equivalent)
The earth leakage breaker should be used in combination with a local switch.
Use a local switch with at least 3 mm (1/8 in) contact separation in each pole.
Do not connect the power cables L1, L2, and L3 to N. Ensure the correct phase sequence.
If the power cable is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
Use dedicated power cables for the outdoor unit and indoor unit.
Power cable size, device capacity, and system impedance
(If local regulations do not specify the minimum power cable size or device capacity, follow the values in the table
below.)
Minimum size [mm
2
(AWG)]
Earth leakage breaker
Local switch (A)
Overcurrent
breaker
(NFB) (A)
Maximum
allowable system
impedance
Power
cable
Power cable
after branching
point
Earth
wire
Capacity Fuse
Outdoor
unit
(E)M200 4.0 (12) 4.0 (12)
30 A 100 mA 0.1 sec.
or less
25 25 30 *
3
(E)M250 4.0 (12) 4.0 (12)
30 A 100 mA 0.1 sec.
or less
32 32 30 *
3
(E)M300 4.0 (12) 4.0 (12)
30 A 100 mA 0.1 sec.
or less
32 32 30 *
3
(E)M350 6.0 (10) 6.0 (10)
40 A 100 mA 0.1 sec.
or less
40 40 40 0.26
(E)M400 10.0 (8) 10.0 (8)
60 A 100 mA 0.1 sec.
or less
63 63 60 0.20
(E)M450 10.0 (8) 10.0 (8)
60 A 100 mA 0.1 sec.
or less
63 63 60 0.19
(E)M500 10.0 (8) 10.0 (8)
60 A 100 mA 0.1 sec.
or less
63 63 60 0.16
Total
operating
current of
the indoor
units
F0 ≤ 16 A *
1
1.5 (16) 1.5 (16) 1.5 (16)
20 A current sensitivity
*
2
16 16 20 (IEC 61000-3-3)
F0 ≤ 25 A *
1
2.5 (14) 2.5 (14) 2.5 (14)
30 A current sensitivity
*
2
25 25 30 (IEC 61000-3-3)
F0 ≤ 32 A *
1
4.0 (12) 4.0 (12) 4.0 (12)
40 A current sensitivity
*
2
32 32 40 (IEC 61000-3-3)
*1 Use the larger value of F1 or F2 as the value of F0.
F1 = Total of each indoor unit's maximum current × 1.2
F2 = {V1 × (Quantity of Type 1)/C} + {V1 × (Quantity of Type 2)/C} + {V1 × (Quantity of Type 3)/C} + {V1 × (Quantity of Type 4)/C}
*2 Current sensitivity is calculated using the following formula.
G1 = (V2 × Quantity of Type 1) + (V2 × Quantity of Type 2) + (V2 × Quantity of Type 3) + (V2 × Quantity of Type 4) +
(V3 × Power cable length (km))
*3 Meets technical requirements of IEC 61000-3-3.
*4 When air flow decrease is detected of a circulation fan beside the HBC controller installed at the height of less than 1.8 m from the ground,
the system must be powered off within 10 seconds from the detection. Before powering off the system, connect the contactor to the power
cable of the outdoor unit and open the contactor. (Make sure to select the appropriate contactor, considering the breaker capacity.)
~220–240 V
L, N
3N~380–415 V
L1, L2, L3, N