–122–
Checking
code
6607
(continued)
Meaning, detecting method
System
compo-
sition
Generating
unit address
Display of
trouble
Detecting
method
Cause Checking method & countermeasure
No ACK error When no-ACK signal is detected 6 consecutive intervals of 30 seconds by
transmission side controller, the transmission side detects error.
Note: The address/attribute shown on remote controller indicates that
the controller is not sending acknowledgement signals (ACK).
1 Outdoor
unit (OC)
2 BC
controller
<master>
(BC)
3 BC
controller
<slave>
(BS)
4 Indoor
unit (IC)
5 Remote
controller
(RC)
Remote
control-
ler (RC)
Remote
control-
ler (RC)
Remote
control-
ler (RC)
Remote
control-
ler (RC)
Remote
control-
ler (RC)
No reply
(ACK) at
OC
transmis-
sion to BC
No replay
(ACK) at
BC <master>
transmis-
sion to IC
No reply
(ACK) at
BC <slave>
transmis-
sion to BC
<master>
No reply
(ACK) at IC
transmis-
sion to RC
No reply
(ACK) at
RC
transmis-
sion to IC
Same as that for single refrigerant system.
Same as that for single refrigerant system.
Same as that for single refrigerant system.
1) Cause of 1) ~ 5) “Cause for single refriger-
ant system”.
2) Disconnection or short circuit of transmission
line of OC terminal block for centralized con-
trol (TB7).
3) Shut down of OC unit power source in one
refrigerant system.
4) Neglecting to insert OC unit power supply
connector (CN40).
5) Inserting more than 2 sets of power supply
connector (CN40) for centralized control use.
For generation after normal operation conduct-
ed once, the following causes can be suspected.
Total capacity error (7100)
Capacity code setting error (7101)
Connecting set number error (7102)
Address setting error (7105)
1) Cause of 1) ~ 3) “Cause for single refri- gerant
system”.
2) Disconnection or short circuit of transmission
line of OC terminal block for centralized con-
trol (TB7).
3) Shut down of OC unit power source of one
Same as measure for single refrigerant
system.
Same as measure for single refrigerant
system.
Same as measure for single refrigerant
system.
a) Shut down both OC and IC power
sources simultaneously for 5 minutes
or longer and then switch on again.
It will return to the normal state in an
accidental case.
b) Check 1) through 5) for the causes of
the problem. Remedy the problem if
found.
c) Check other remote controller or OC
unit LED for troubleshooting.
Trouble
Correct the problem
according to the con-
tent of check code.
No trouble Faulty indoor con-
troller
a) Shut down the power source of OC
for over 5 minute, and then switch on
again.
Normal state will be returned in case
of accidental trouble.
b) Check 1) through 5) for the causes of
the problem. Remedy the problem if
found. When the normal state cannot
be restored, check for 1) ~ 5) for the
cause.