Mitsubishi City Multi PURY-P400 - Oil Return Control (Electronic Expansion Valve); Defrosting Control

Mitsubishi City Multi PURY-P400
145 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
Item
At start of compressor
Compressor stopped during cool-
ing or heating mode
After operation has been stopped
During defrosting ((*1) in Fig. below)
During oil recovery operation
When low pressure (Ps) has
dropped during lower limit fre-
quency operation(15 minutes af-
ter start)
When the high pressure (Pd) is
risen up during lower limit fre-
quency operation (3 minutes after
starting)
Ps 0.196 MPa
Pd
2.35 MPa and
after 30 seconds
* Example of operation of SV1
Compressor
Bypass
solenoid
valve (SV1)
(4-minute)
(2-minute) (4-minute) (3-minute)
Start
Thermo.
OFF
Thermo.
ON
Defrost
Stop
ON OFF
SV1
ON for 4 minutes
ON
ON for 3 minutes
ON
ON during oil recovery operation af-
ter continuous low-frequency com-
pressor operation.
ON
Ps < 0.098 MPa
Pd
2.65 MPa
OFF
SV4a
Normally ON
3) Capacity control solenoid valve (SV22, SV32). :P500 only
Operation of solenoid valve
Solenoid valve
SV22
SV32
COMP
SV22 SV32
Coil Valve Coil Valve
OFF Open OFF Closed
ON Closed ON Open
Status
Full-load
(Operating at 100 %
capacity)
Un-load
(Capacity control
operation)
Pd 2.70 MPa
Pd 2.35 MPa
and after 30
seconds.
130°C
(No. 1 compressor)
115°C
(No. 2 compressor)
Td
>
and
Pd > 1.96 MPa
or
Ps < 0.34 MPa
115°C
(No. 1 compressor)
100°C
(No. 2 compressor)
Td
When the discharge temperature
(Td) rises
2) Bypass solenoid valves (SV1, SV4) [Both SV1 and SV4 are on (open)]