72
(4) LEV
Outdoor unit
The valve percentage opening changes in proportion to the number of pulses.
(Connections between the outdoor units MAIN board and SLEV, (PURY-P400·500YEM-A))
Output (phase)
Output states
Output pulses change in the following orders:
When the valve is Closed 123456781
When the valve is Open 876543218
*1. When the LEV percentage opening does not change,
all the output phases are off.
2. When the output is out of phase or stays on, the motor
cannot run smoothly, and it jerks and vibrates.
* When the power is switched on, a 520-pulse valve
opening signal is output to locate the valves position to
ensure that it is at point A. (The pulse signal is output
for approximately 17 seconds.)
* Normal operation of the valve does not produce noise
or vibration. When the valve is locked, it produces
noise.
* Hold the tip of a screwdriver against it and the handle
against your ear, and listen for operating sounds.
* If there is liquid refrigerant inside the LEV, the sound
may become lower.
Valve Opening Angle (Flow Rate)
Pulse Count
Valve Opening
A
Fully Open
480 pulses
Valve Closing
Pulse Signal Output and Valve Operation
1234567 8
ø1 ON OFF OFF OFF OFF OFF ON ON
ø2 ON ON ON OFF OFF OFF OFF OFF
ø3 OFF OFF ON ON ON OFF OFF OFF
ø4 OFF OFF OFF OFF ON ON ON OFF
LEV Valve Closing and Valve Opening Operations