Mitsubishi City Multi PURY-P400 - 3 LEV and Solenoid Valve Troubleshooting Flow Chart

Mitsubishi City Multi PURY-P400
145 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
95
No cooling
No heating
Check for disconnected or loose
connectors.
Is there a problem?
Operate in cooling or heating (1 system
only when there are plural systems)
Cooling or heating
operation?
Heating operation
Note 1
Check if LEV 1 is fully open
LEV 1 fully open?
LEV3 are not
controlled
Check if LEV 1 is fully closed.
Ye s
Note 2
No
Ye s
No
Ye s
No
Ye s
No
Ye s
Check if LEV3 is controlled by
superheat.
LEV3 is controlled.
Check if SVM1 is ON.
SVM1 ON
Check if SVA, SVC are ON.
SVA, SVC ON
Check if SVB is OFF.
SVB OFF
Check if LEV 3 are controlled by
differential pressure.
Completion
Check SVB
Check SVA, SVC
Check SVM1
Check LEV3
Correct the problem.
Check LEV1
SVB ON
Check if SVB is ON.
SVA, SVC OFF
Check if SVA, and SVC are OFF.
SVM1 OFF
Check if SVM1 is OFF.
Is LEV 1 fully
closed?
Ye s
No
Note 2
No
No
No
Ye s
Ye s
Ye s
Note 3Note 3
No
Ye s Ye s
No
3) LEV, Solenoid Valve Troubleshooting Flow Chart