PARAMETERS
106
4.2.29 Input filter time constant (Pr. 74)
Pr. 74 "filter time constant"
You can set the input section's internal filter constant for an external voltage or current
frequency setting signal.
!
Effective for eliminating noise in the frequency setting circuit.
!
Increase the filter time constant if steady operation cannot be performed due to
noise. A larger setting results in slower response. (The time constant can be set
between approximately 1ms to 1s with the setting of 0 to 8. A larger setting results in
a larger filter time constant.)
Parameter
Number
Factory
Setting
Setting
Range
74 1 0 to 8
4.2.30 Reset selection/disconnected PU detection/PU stop
selection (Pr. 75)
Pr. 75 "reset selection/disconnected PU detection/PU stop selection"
You can select the reset input acceptance, control panel (FR-PA02-
02
) or PU (FR-
PU04) connector disconnection detection function and PU stop function.
!
Reset selection :You can select the reset function input timing.
!
PU disconnection detection :When it is detected that the control panel
(FR-PA02
-02)
/PU(FR-PU04) is disconnected from the
inverter for more than 1 second, the inverter outputs an
alarm code (E.PUE) and comes to an alarm stop.
!
PU stop selection : When an alarm occurs in any operation mode, you can
stop the inverter from the PU by pressing the
STOP
RESET
key.
Parameter
Number
Factory
Setting
Setting Range
75 14 0 to 3, 14 to 17