INSTALLATION AND WIRING
17
Type Symbol
Terminal
Name
Description
Contact
A, B, C Alarm output
Contact output indicating that the output has
been stopped by the inverter protective
function activated. 230VAC 0.3A, 30VDC
0.3A. Alarm: discontinuity across B-C
(continuity across A-C), normal: continuity
across B-C (discontinuity across A-C).
RUN
Inverter
running
Switched low when the inverter output
frequency is equal to or higher than the
starting frequency (factory set to 0.5Hz,
variable). Switched high during stop or DC
injection brake operation (*1).
Permissible load 24VDC 0.1A.
FU
Frequency
detection
Switched low when the output frequency has
reached or exceeded the detection frequency
set as appropriate. Switched high when below
the detection frequency (*1).
Permissible load 24VDC 0.1A
Output
terminal
function
choices
(Pr. 190 to
Pr. 192)
change
terminal
functions.
Open collector
SE
Open collector
output
common
Common to the RUN and FU terminals.
Pulse
FM
(200V
and
100V
class
inverters)
For meter
Factory setting of output item:
Frequency
Permissible load current 1mA
1440 pulses/s at 60Hz
Output signals
Analog
AM
(400V
class
only)
Analog signal
output
One selected from output
frequency, motor current
and output voltage is
output (*2). The output
signal is proportional to
the magnitude of each
monitoring item.
Factory setting of output item:
Frequency
Output signal 0 to 10 VDC
Permissible load current 1mA
Communication
RS-485
PU connector
With the control panel connector, communication can be
made using the RS-485 protocol.
!
Conforming Standard : EIA Standard RS-485
!
Transmission format : Multi-drop link
!
Communication speed : Maximum 19200 bps
!
Overall length : 500m (1640.40 feet)
*1: Low indicates that the open collector output transistor is on (conducts). High
indicates that the transistor is off (does not conduct).
*2: Not output during inverter resetting.
2