11.
OPERATION
11.8
LocaVAuto
External
Signal
Selection
Mode
In this mode, the operation mode can
be
modified
by
turning ON/OFF an external signal (terminal
RH). Since the operation
mode
can
be
changed by the external signal, erroneous mode switching
can
be
avoided.
Set
Signal
value
(RH
and
SD)
Flxsd
mode
Comment
I
~
1
Close
I
mode
External
operatm
1
Changing
to
the
PU
operation mode is impossible.
I
8
Open
Changing
to
the
external
operation
mode
is
PU
operation
mode
impo~ible,
If the circuk acw terminals RH and
SD
is closed while in the
PU
operation
mode,
the operation
mode is forcibly changed
to
the external operation mode. If it is opened, the operation mode is
forcibly changed
to
the
PU
operation mode.
Note that this
mode
change is possible only while the inverter is stopped. The
mode
change
is
not allowed while
the
inverter is operating.
Note:
If
'8'
is
set
for Pr.79, the function of the terminal RH (multiple speed setting (high-speed))
is changed to the locaVauto external selection function. In this setting, the ordinary func-
tion of the terminal RH does not work.