PURY-HP-T(S)KMU,-Y(S)KMU (September 2014)
H2i-R2-13
© 2014 Mitsubishi Electric US, Inc.
2. EXTERNAL DIMENSIONS
PURY-HP144, 192TSKMU-A-H(-BS)
Unit : mm(in)
30 (1-3/16)
1220 (48-1/16) 1220 (48-1/16)
1650 (64-31/32)
740 (29-5/32)
Front view
Left view
Outdoor unit 2Outdoor unit 1
To BC controller
To BC controller
a
b
e
f
c
d
Twinning pipe(High pressure)
<optional parts>
Twinning pipe(Low pressure)
<optional parts>
Intake
air
Intake
air
Discharge air
Intake
air
Low pressure
Unit model
Component
unit model
ø15.88(5/8) ø19.05(3/4)ccee
ddff
High pressure
HP72 HP96
Twinning Kit
~Outdoor unit
HP72 HP96
(Note 5) (Note 5)
--
ø19.05(3/4)
ø19.05(3/4)
HP144 HP192
Low pressure
Twinning pipe connection size
Outdoor unit 1
Component unit name
Package unit name
BC controller~Twinning pipe
a
b
High pressure
Outdoor Twinning Kit(optional parts)
CMY-R100CBK2
Outdoor unit 2
PURY-HP144TSKMU-A-H(-BS) PURY-HP192TSKMU-A-H(-BS)
PURY-HP72TKMU-A-H(-BS) PURY-HP96TKMU-A-H(-BS)
PURY-HP72TKMU-A-H(-BS) PURY-HP96TKMU-A-H(-BS)
ø28.58(1-1/8)
ø22.2(7/8)
ø15.88(5/8)
ø22.2(7/8)
Note 1. Connect the pipes as shown in the figure above. Refer to the table aboveforthe pipe size.
2. Twinning pipe (High pressure) should not be tilted more than 15 degrees from the horizontal plane.
Be sure to see the Installation Manual for details of Twinning pipe installation.
3. The pipe section before the Twinning pipe (section "a" in the figure) must have at least 500mm(19-11/16) of straight section
(*including the straight pipe that is supplied with the Twinning pipe).
4. Only use the Twinning pipe by Mitsubishi (optional parts).
5. Connect the outdoor unit 1 with the Twinning pipe (Low pressure) (section "d" in the figure).