Operating temperature range
ڦ Cooling
ڦ Heating
Decline in cooling and heating capacity or operation stop may occur when the outdoor unit is installed in
places where natural wind can increase or decrease its design air flow rate.
-15°CDB
Usage range in cooling
Usage range in heating
Indoor air temperature°CWB
Outdoor air temperature°CWB
Outdoor air
temperature°CDB
Indoor air
temperature
°CDB
“CAUTION” Cooling operation under low outdoor air temperature conditions
Micro KXZ-W models can be operated in cooling mode at low outdoor air temperature condition within above temperature range.
However in case of severely low temperature conditions if the following precaution is not observed, it may not be operated in spite
of operable temperature range mentioned above and cooling capacity may not be established under certain conditions.
[Precaution]
In case of severely low temperature condition
1) Install the outdoor unit at the place where strong wind cannot blow directly into the outdoor unit.
2) If there is no installation place where can prevent strong wind from directly blowing into the outdoor unit, mount the flex flow
adapter (prepared as option part) or like such devices onto the outdoor unit in order to divert the strong wind.
[Reason]
Under the low outdoor air temperature conditions of -5°C or lower, the outdoor fan is controlled at lower or lowest speed by outdoor
fan control, but if strong wind directly blow into the outdoor unit, the outdoor heat exchanger temperature will drop more.
This makes high and low pressures to drop as well. This low pressure drop makes the indoor heat exchanger temperature to drop and
will activate anti-frost control at indoor heat exchanger at frequent intervals, that cooling operation may not be established for any
given time.
43°CDB