Code
No.
Contents of data display Data display range
Minimum
unit
Remarks
<Anomalous counter information>
C70 Counter · Sensor wire disconnected 0 - 3 1
C71 Counter · High pressure protection 0 - 5 1
C72
Counter · Anomalous low pressure
③
(During
operation)
0 - 5 1
C73 Counter · Anomalous low pressure
①
(During stop) 0 - 5 1
C74 Counter · Discharge pipe 1 anomalous temperature 0 - 5 1
C75 Counter · Anomalous FMo1 stop 0 - 5 1
C76 (Spare)
C77 Counter · Current cut (CM1) 0 - 4 1
C78 Counter · Compressor 1 starting failure 0 - 20 1
C79 Counter · Inverter 1 comunication error 0 - 4 1
C80 (Spare)
C81 (Spare)
C82 Counter · Inverter 1 desynchronism error 0 - 127 1
C83 Counter · Inverter 1 comunication error cumulative 0 - 127 1
1
1
C84 Counter · Indoor/outdoor comunication error 0 - 255
1
C85 Counter · CPU reset 0 - 255
C86 (Spare)
C87 (Spare)
C88 (Spare )
C89 (Spare)
C90 (Spare)
C91 (Spare)
C92 (Spare)
C93 (Spare)
C94 Counter·Liquid flooding
<Others>
C95 (Spare)
C96 Data reset
C97 Program·sub version 0 - 991
0 - 3
–
C98 Program · POL version 0.00 - 9.99 0.01
C99 (Spare)
P02 Outdoor fan snow protection control
0 : (Factory default)
0,1 -
4
–
dilavni lortnoc noitcetorp wons naf roodtuO :0
(Factory default)
1
: Outdoor fan snow protection control
P03
Outdoor fan snow protection control
ON time setting
30 : (Factory default)
10, 30 - 600 [Sec]
30
valid
Changes like 10, 30, 60 90 … 600
P04 Demand ratio change value
OFF : (Factory default)
OFF,000,040,
060,080
0: OFF, 1: 0%, 2: 40%. 3: 60%, 4: 80%
Factory default is 0: OFF.
P05 Silent setting
0 : (Factory default)
0 - 9
1
P06 External output function quota
0 : (Factory default)
0 - 9
1
P07
External input (CnS1) function
quota
0 : (Factory default)
0 -
1
P08
(Spare)
P09
(Spare)
P10
(Spare)
Code
No.
Contents of data display Data display range
Minimum
unit
Remarks
<User setting>
P00 Continuous heating operation control –
P01 Operation preference switching
0 : (Factory default)
0,1,2,3
0 : (Factory default)
0,1,2
–
0: First unit's operation mode
1: Last unit's operation mode
2: Priority
unit's mode
q
0 : Invalid
1 : Defrost interval extension control
2 : Continuous heating control
<New Superlink setting>
P30
Superlink communication
satus
0,1 –
0: Current Superlink
1: New Superlink
P31 Start automatic address setting
0 : (Factory default)
0,1
–
0: Automatic address setting standby.
1: Automatic address setting start.
P32 Input starting indoor address
1 : (Factory default)
0 - 127
1
Specify the starting indoor address connected in one
refrigerant system for automatic address setting.
P33
Input the number of connected
indoor unis
1 : (Factory default)
1 - 24 (*)
1
Specify the number of indoor units connected in one
refrigerant system for automatic address setting.
(*) Maximum connectable number of indoor units
for each oudoor unit
P34 Polarity difinition
0 : (Factory default)
0,1
–
0: Network polarity not defined
1: Network polarity defined
P35 (Spare)
P36 (Spare)
-
203
-