Code
No.
Write content
Record data
Data write range
Unit of
write
Number of
bytes
Content
37 FM01 Fan speed command 0 - 65535 10min
-1
2
38 (Spare)
39 EEVH1 opening degree 0 - 65535 1 pulse 2
40 EEVSC opening degree 0 - 65535 1 pulse 2
41 Compressor target cooling low
pressure
0.00 - 2.00 0.01MPa 1
42 Compressor target heating high
pressure
0.00 - 4.15 0.01MPa 2
43 Outdoor EEVH target overheat 0 - 25.5 0.1°C 1 Actual range: 5°C – 11°C
44 Outdoor EEVH initial learning
opeing position
0 - 255 1 pulse 1
45 Outdoor EEVSC target overheat 0 - 25.5 0.1°C 1
46 (Spare)
47 (Spare)
<PCB hardware input>
48 External input 1 Bit0 63H1 0: Open, 1: Short-circuit
Bit1 (Spare)
Bit2 CnS1 0: Open, 1: Short-circuit
Bit3 (Spare)
Bit4 (Spare)
Bit5 (Spare)
Bit6 (Spare)
Bit7 (Spare)
49 DIP switch [SW3]
1 Bit0 SW3-1 0 : OFF, 1 : ON
Bit1 SW3-2 0 : OFF, 1 : ON
Bit2 SW3-3 0 : OFF, 1 : ON
Bit3 SW3-4 0 : OFF, 1 : ON
Bit4 SW3-5 0 : OFF, 1 : ON
Bit5 SW3-6 0 : OFF, 1 : ON
Bit6 SW3-7 0 : OFF, 1 : ON
Bit7 SW3-8 0 : OFF, 1 : ON
50 DIP switch [SW4] 1 Bit0 SW4-1 0 : OFF, 1 : ON
Bit1 SW4-2 0 : OFF, 1 : ON
Bit2 SW4-3 0 : OFF, 1 : ON
Bit3 SW4-4 0 : OFF, 1 : ON
Bit4 SW4-5 0 : OFF, 1 : ON
Bit5 SW4-6 0 : OFF, 1 : ON
Bit6 SW4-7 0 : OFF, 1 : ON
Bit7 SW4-8 0 : OFF, 1 : ON
51 DIP switch [SW5] 1 Bit0 SW5-1 0 : OFF, 1 : ON
Bit1 SW5-2 0 : OFF, 1 : ON
Bit2 SW5-3 0 : OFF, 1 : ON
Bit3 SW5-4 0 : OFF, 1 : ON
Bit4 SW5-5 0 : OFF, 1 : ON
Bit5 SW5-6 0 : OFF, 1 : ON
Bit6 SW5-7 0 : OFF, 1 : ON
Bit7 SW5-8 0 : OFF, 1 : ON
-