Code
No.
Write content
Record data
Data write range
Unit of
write
Number of
bytes
Content
<Control status>
62 Control status
Oil return
0 - 2 – 1 0 None
1 Oil return ON
63 Control status
Defrost condition
0 - 3 – 1 0 None
1 Temperature condition
2 Time condition
64 Control status
Defrost status
0 - 4 – 1 0 None
1 Defrost status 1
2 Defrost status 2
3 Defrost status 3
4 Defrost status 4
65 Control status
Cooling low
pressure anomaly
recovering status
0 - 4 – 1 0 None
1 Status 1
2 Status 2
3 Status 3
4 Status 4
66 Control status 1 1 Bit0 Test run control implementing
0: Normal, 1: Implementing
Bit1 Demand control implementing
0: Normal, 1: Implementing
Bit2 Silent mode implementing
0: Normal, 1: Implementing
Bit3 (Spare)
Bit4
0: Normal, 1: Implementing
Bit5 (Spare)
Bit6
Fresh Air Intake Pre-treating
Unit Control
control at start/stop
Implementing pump down
0: Normal, 1: Implementing
Bit7
Low ambient air temperature
control implementing
0: Normal, 1: Implementing
67 Control status 2 1
Bit0
Pump-down control for
removal of unit implementing
0: Normal, 1: Implementing
Bit1 Compressor dilution protection
0: Normal, 1: Implementing
Bit2
(Spare)
Bit3
Forced out refrigerant from
indoor heat exchanger
0: Normal, 1: Implementing
Bit4 EEVKIT multi-setting status
0: Normal, 1: Implementing
Bit5 (Spare)
Bit6 (Spare)
Bit7 (Spare)
-
210
-