Code
No.
Write content
Record data
Data write range
Unit of
write
Number of
bytes
Content
<Error counter information>
72 Control status HP (63H1) anomaly counter 0 - 5 1 1
73
Control status LP anomaly counter while
running
0 - 5 1 1
74
Control status LP anomaly counter while
stopping
0 - 5 1 1
75
Control status Td1 error counter
0 - 5 1 1
76
Control status DC fan motor 1 error counter
0 - 5 1 1
77
(Spare)
78
Control status sensor wire disconnected
counter
0 - 3 1 1
79
Control status INV1 current cut error counter
0 - 4 1 1
80
Control status INV1 starting failure counter
0 - 20 1 1
81
Control status INV1 communication error
counter
0 - 4 1 1
82
Control status INV1 desynchronism error
counter
0 - 127 1 1
83
Control status INV1 communication error
counter cumulative
0 - 255 1 1
0 - 127 1 1
84
(Spare)
85
Control status liquid flooding counter
<Setting value display>
86
Operation priority switching outdoor fan
snow protection control
0 - 3 1
0 First push priority
1 Last push priority
2
Priority of master units
setting operation mode
3
Priority of required major
operation mode
87 Outdoor fan snow protection control
0,1 1
0 Invalid
1 Valid
88
Outdoor fan snow protection control ON
time setting
30: (Factory default)
10, 30 – 600 [sec.]
10 sec. 1
89
Demand ratio change value OFF, 000, 040, 060,
080
Factory default 0: OFF
1
90 Silent mode setting 0 - 9 1
91
CnS1 function quota value 0 - 20 1
92 (Spare)
93 (Spare)
94 (Spare)
95 External output function quota 0 - 9 1
Code
No.
Write content
Record data
Data write range
Unit of
write
Number
of bytes
Content
<Other>
<Indoor unit information>
105 1 Bit0
Bit1
Bit2
Bit3
Bit4 (Spare)
Bit5 (Spare)
Bit6 (Spare)
Bit7 (Spare)
(Spare)
(Spare)
(Spare)
(Spare)
106 Registered indoor 1 – 8 operation
mode
0 - 4 8 0 Auto
1 Humidifying
2 Cooling
3 Fan
4 Heating
107 Registered indoor 1 – 8 request Hz 0 - 255 1Hz 8
108 Registered indoor 1 – 8 answer Hz 0 - 255 1Hz 8
<Check operation information>
109 Check operation status 0 - 7 1 0 Normal
1 Check operation
starting condition
insufficient
2 Check operation
preparation
operation
3 Check operation
implementation
4 Check operation
interrupted
5 Service valve
closing failure
6 Indoor unit failure
7 Check operation
normal ending
-
213
-
'20 • KX-T-373

Table of Contents