236
-
Error code
Remote control:
7-segment display:
LED Green Red
Indoor
Outdoor
Content
E5
Communication error during operation
Keeps flashing
*See below
Keeps flashing
2 time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Does
the remote control LCD
becomes normal?
Reset the power source and restart.
YES
NO
* In case that indoor unit red LED stays OFF
Is the
connection of signal wires
at the outdoor unit side
OK?
Is the
connection of signal wires
(between indoor and outdoor units)
OK?
Does the
remote control LCD
becomes normal?
Note (1) Check the connection (disconnection, looseness)
of signal wires at outdoor unit terminal block
Reset the power source and restart.
Note (2) Check the connection (disconnection, looseness,
brakage) of signal wires (between indoor and
outdoor units)
YES
NO
YES
NO
YES
NO
* In case that indoor unit red LED flashes 2 times
Repair signal wires.
Repair signal wires.
Go to the diagnosis of
WAIT
/Searching IU (1).
Unit is normal.
(Malfunction by temporary
noise, etc.)
Outdoor unit control PCB anomaly
(Network communicaion
circuit anomaly)
→ Replace it.
Unit is normal.
(Malfunction by temporary
noise, etc.)
2. Error detection method
When the communication
between indoor and outdoor
units is interupted for more than
2 minutes
3
.
Condition of error displayed
When this anomaly is detected
during operation.
4. Presumable cause
• Unit address No. setting error
•
Remote control wires broken
•
Poor connection/disconnection
of remote control wires
•
Indoor unit control PCB anomaly
Note:
When the pump down switch is turned on, communication between indoor and outdoor units is cancelled so that
"Communication error E5" will be displayed on the remote control and indoor unit control PCB, but this is normal.