269
-
'20 • KX-T-373
E59
E59
Compressor startup failure
Stays Off
1. Applicable model
5. Troubleshooting
Outdoor unit
Diagnosis Countermeasure
Is power
Single phase : AC198-264 Vrms
Three phase : AC342-457 Vrms
source voltage OK?
Is the
pressure balance at
starting OK?
Is the
insulation resistance
and resistance between
terminals of
compressor
OK ?
Is power transistor
module OK?
Is the
output of inverter
checker OK ?
Does it start?
Does
compressor startup?
Save data for 30 minutes before stoopping in Mente PC.
Try to restart several
times.
In case that the compressor
does not start at all and no
sound or vibration is heard
Start up by disconnecting
connector of outdoor
fan motor
Note : Several times restarting
may recover it, because liquid
refrigerant migrated in the
compresser is discharged from
the compressor.
After power OFF, turn JSW10-4 on the inverter PCB ON
and connect the inverter checker. And then power ON again.
(Regarding the checking method of inverter PCB with
inverter checker, refer to page 277 in detail)
Check and save the data of
operating conditions.
Replace outdoor fan motor.
Check power source
voltage.
Check refrigerant amount
and refrigerant circuit.
Repalce compressor.
Replace inverter PCB.
Replace inverter PCB.
Repalce compressor.
2. Error detection method
If it fails to change over to the
operation for rotor detection of
compressor motor
3
.
Condition of error displayed
If compressor fails to startup for
20 times (10 patterns x 2 times).
(It is availabel to reset by
remote control after 3 minutes
delay)
4. Presumable cause
Faulty fan motor
Faulty outdoor unit control PCB
Faulty inverter PCB
Anomalous power source
voltage
Nonconformity of refrigerant
amount and refrigerant circuit
Faulty compressor
Note: Insulation resistance
The unit is left for long period without power source or soon after installation, insulation resistance may decrease to
several or lower due to the liquid refrigerant migrated in the refrigerant oil in compressor. If the electric leakage
breaker is activated due to low insulation resistance, check followings.
Check whehter the insulation resistance can recover or not, after 6 hours has passed since power ON.
(By energize the crankcase heater, liquid refrigerant migrated in the refrigerant oil in compressor can be evaporated.)
Check whether the electric leakage breaker conforms to high-hermoni .
(As this units has inverter, in order to prevent from improper operation, be sure to use the breaker of high-hermonic one.)
Error code
Remote control:
7-segment display:
LED Green Red
Indoor
Outdoor
Content
NONO
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YESYES
NO (Inverter PCB is defective)NO (Inverter PCB is defective)
Error code
Remote control:
7-segment display:
LED Green Red
Indoor
Outdoor
Content
E63
E63
Emergency stop
Keeps flashing
Stays Off
Keeps flashing
1 time flash
1. Applicable model
5. Troubleshooting
Indoor unit
Diagnosis Countermeasure
Is the
remote control setting
of Emergency Stop
"Valid"?
Is ON
signal inputted to the
CnT terminal of indoor
unit control PCB?
Save data for 30 minutes before stopping in Mente PC
NO
NO
YES
Check and save the data of
operating conditions.
Check the conditions
whether it occurs
immediately after the power
on or during operation.
Replace remote control
PCB.
Replace indoor unit control
PCB.
Check the cause of
emergency stop.
(It is better to have the data
for 30 minutes before
stopping, when instructing
the installer.)
2. Error detection method
When ON signal is inputted
to the CnT terminal of indoor
unit control PCB
3
.
Condition of error displayed
Same as above
4. Presumable cause
Factors for emergency stop
Note: Indoor unit detected emergency stop signal gives command "all stop"