300
-
'20 • KX-T-373
1
Control plural indoor units with one remote control
Up to 16 indoor units can be connected.
1.
Connect the XY terminal with 2 cores wire. As for the
size, refer to the following note.
2. For Packaged air-conditioner series, set the indoor
unit address with SW2 on the indoor unit PCB from
[0] to [F] so as not to duplicate.
For the shop series
For VRF series, set the indoor unit address with SW1, SW2 and SW5-2 on the indoor unit PCB from [000]
to [127] so as not to duplicate.
For the building air- conditioning and gas heat pump series
Set the indoor unit and outdoor unit numbers by manually specifying the addresses.
Use the rotary switches SW1 and SW2 provided on the indoor unit PCB (printed circuit board) to set the
indoor unit numbers so that they are not duplicated.
Master/Slave setting when using plural remote control
Up to two receivers can be installed in one indoor unit group.
Wireless remote control's operable area
1. Standard reachable area of the signal
[condition] Illuminance at the receiver: 300lux
2. Correlation between illuminance at the receiver
and reachable area of the signal in a plain view.
The drawing in the right shows the correlation
between the reachable area of the signal and
illuminance at the receiver when the remote
control is operated at 1.0m high under the
condition of ceiling height of 2.4m. When
the illuminance becomes double, the area is
narrowed down to two thirds.
3. Installation tips when several receivers are installed close
Minimum distance between the indoor units which can avoid cross communication is 5m under the condition
of 300lux of illuminance at the receiver.
Backup switch
A backup switch is provided on the receiver. Even
when the operation from the wireless remote
control lost, or control failure), still it possible
to operate as temporary means. Press the switch
directly when operating it.
1. The air-conditioner starts the operation with
the condition of Auto mode, 23°C of set
point, High fan speed and horizontal louver
position.
2. The air-conditioner stops the operation when
the switch is pressed when in operation.
Cooling test run operation
Transmit a cooling operation command with the wireless remote control unit, while the backup switch
on the receiver is depressed.
If the backup switch on the receiver is pressed during a test run, it will end the test run.
If you cannot operate the unit properly during a test run, please check wiring by consulting with
inspection guides.
How to read the 2-digit display
On the receiver of a wireless kit, a two-digit (7-segment) display is provided.
1. An indication will be displayed
for one hour after power on.
2. An indication will be displayed for 3.5 seconds after transmitting a STOPcommand from the
wireless remote control or the operation of the backup switch to stop the unit.
3. An indication appearing in (1) or (2) above will go off as soon as the unit starts operation.
4. When there are no error records to indicate, addresses of all the connected units are displayed.
5. When there are some error records remaining, the error records are displayed.
6.
Error records can be cleared by transmitting a "STOP" command from the wireless remote control,
while the backup button is pressed.
Receiver
Receiver (continued)
Indoor unit
Receiver
SW2[Master]
Receiver
SW2[Slave]
Remote control line
(No polarity)
Reachable area of the signal
Ceiling surface
4m 3m 2m 1m 0 1m 2m 3m 4m
1m
1.4m
2.4m
Switch Setting Function
SW2
ON Master
OFF Slave
Restrictions on the thickness and length of wire
(Maximun total extension 600m.)
Standard Within 0.3 mm² × 100m
Within 0.5 mm² × 200m
Within 0.75mm² × 300m
Within 1.25mm² × 400m
Within 2.0 mm² × 600m
Terminal block
Wireless remote control
Indoor unit (1)
Address (0)
Indoor unit (2)
Address (1)
Indoor unit (16)
Address ( F )
Receiver
The receivable area of the
signal when the illuminance
at the receiver is 300lux
The receivable area of the
signal when the illuminance at
the receiver is 600lux
Wireless remote control
Wireless remote control (continued)
Installation tips for the remote control holder
Fix the remote control holder using the screws supplied with
this product.
* Precautions for installing the holder
Adjust the position so that it is upright.
Ensure that the screw heads are not protruding.
Do not attach the holder on plaster wall
How to insert batteries
1. Detach the back lid.
2. Insert the batteries. (two AAA batteries)
3. Reattach the back lid.
Setting to avoid mixed communication
1. Detach the back lid, and remove the batteries.
2. Cut off the switching wire in the battery compartment using nippers.
3. Insert the batteries, and attach the back lid.
Changing the remote control setting
How to change the Auto Run setting
The Auto Run mode is not available on the building air-conditioning and gas heat
pump series (excluding the cooling/heating free multi system).
When using the remote control to operate those models, set the remote control to
disable the Auto Run mode.
To disable the Auto Run mode, press the
ACL
switch
while holding down the
MODE
button, or insert batteries while holding down the
MODE
button.
* Note: Once the batteries are removed, the setting is reset to the factory default.
.evoba debircsed spets eht taeper ,devomer era seirettab eht nehW
Indoor function settings
1. How to set indoor functions
Press the ON/OFF button to stop the unit.
Press the desired one of the buttons shown item 2. while holding down the
FUNCTION SETTING switch.
Use the selection buttons, and , to change the setting.
Press the SET button.
The buzzer on the remote control signal receiver beeps twice, and the LED
Wood screw
Cutting
Holder for
remote control
Ensure the correct
polarity when
inserting.
Auto Run setting
2. Setting details
The following functions can be set.
Button Number indicator Function setting
FAN SPEED
00 Fan speed setting : Standard
01 Fan speed setting : Setting 1 *
02 Fan speed setting : Setting 2 *
MODE
00 Room heating temperature adjustment : Disable
01 Room heating temperature adjustment : +1°C
02 Room heating temperature adjustment : +2°C
03 Room heating temperature adjustment : +3°C
FILTER
00 Filter sign display : OFF
01 Filter sign display : 180 hours
02 Filter sign display : 600 hours
03 Filter sign display : 1000 hours
04 Filter sign display : Operation stop after 1000 hours have elapsed
U/D
00 Anti draft setting : Disable
01 Anti draft setting : Enable
SILENT
00 Infrared sensor setting (Motion sensor setting) : Disable
01 Infrared sensor setting (Motion sensor setting) : Enable
HI POWER
00 Infrared sensor control (Motion sensor control) : Disable
01 Infrared sensor control (Motion sensor control) : Power control only
02 Infrared sensor control (Motion sensor control) : Auto OFF only
03 Infrared sensor control (Motion sensor control) : Power control and Auto OFF
ON TIMER
00 Cooling fan residual-period running : Disable
01 Cooling fan residual-period running : 0.5 hours
02 Cooling fan residual-period running : 2 hours
03 Cooling fan residual-period running : 6 hours
OFF TIMER
00 Heating fan residual-period running : Disable
01 Heating fan residual-period running : 0.5 hours
02 Heating fan residual-period running : 2 hours
03 Heating fan residual-period running : 6 hours
NIGHT
SETBACK
00 Remote control signal receiver LED : Brightness High
01 Remote control signal receiver LED : Brightness Low
02 Remote control signal receiver LED : OFF
* Refer to page 173.
Backup switch
(Up/Down)
Cut