86
Table 6.1 Error Code List for A1SCPUC24-R2 (Continue)
Error Message
Error Code
(D9008)
CPU
States
Error and Cause Corrective Action
"CAN’T
EXECUTE(P)"
(Checked at the
execution of
instruction)
13 Stop
(1) There is no jump
destination or
multiple
destinations
specified by the ,
, , ,
or instruction.
(2) There is a
instruction and no
setting of
subprogram.
(3) Although there is no
instruction, the
instruction
exists in the
program and has
been executed.
(4) The , , ,
, or
instruction has been
executed with its
jump destination
located below the
instruction.
(5) The number of the
instructions is
different from that of
the
instructions.
(6) A instruction is
given within a
loop
causing the
processing to exit
the loop.
(7) Processing exited
subroutine by the
instruction
before execution of
the instruction.
(8) Processing jumped
into a step in a
loop or into
a subroutine by the
instruction.
(9) The instruction
is given in an
interrupt program, a
subroutine program
or in a
loop.
Read the error step by
use of peripheral
equipment and correct
the program at that
step.
(Insert a jump
destination or reduce
multiple destinations to
one.)
CJ
SCJ CALL CALLP
JMP
CHG
CALL
RET
CJ SCJ CALL
CALLP
JMP
END
FOR
NEXT
JMP
FOR to NEXT
JMP
RET
FOR to NEXT
JMP
STOP
FOR to NEXT

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-A A1SHCPU and is the answer not in the manual?

Mitsubishi MELSEC-A A1SHCPU Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-A A1SHCPU
CategoryController
LanguageEnglish

Related product manuals