3.1.1 EMC standards
(1) Regulations regarding emission
*1 QP : Quasi-peak value, Mean : Average value
*2 The programmable controller is an open type device (device installed to 
another device) and must be installed in a conductive control panel.
The tests for the corresponding items were performed while the 
programmable controller was installed inside the control panel.
Standard Test item Test description Value specified in standard
EN61131-2:
2007
CISPR16-2-3
Radiated emission 
*2
Radio waves from 
the product are 
measured.
• 30M-230MHz
QP: 40dBµV/m (10m in 
measurement range) *1
• 230M-1000MHz
QP: 47dBµV/m (10m in 
measurement range)
CISPR16-2-1,
CISPR16-1-2
Conducted emission 
*2
Noise from the 
product to the power 
line is measured.
• 150k-500kHz
QP: 79dB, Mean: 66dB *1
• 500k-30MHz
QP: 73dB, Mean: 60dB