9
(2) Regulations regarding immunity
*1 Programmable controllers are open-type devices (devices designed to be 
housed inside other equipment) and must be installed inside a conductive 
control panel. The corresponding tests were conducted with the 
programmable controller installed inside a control panel.
*2 The accuracy of an analog-digital converter module may temporary vary 
within  10%.
Standard Test item Test description Value specified in standard
EN61131-2:
2007
EN61000-4-2 
Electrostatic 
discharge immunity
*1
Immunity test in 
which electrostatic 
is applied to the 
cabinet of the 
equipment.
• 8kV Air discharge
• 4kV Contact discharge
EN61000-4-3 
Radiated, radio-
frequency, 
electromagnetic field 
immunity *1
Immunity test in 
which electric fields 
are irradiated to the 
product.
80% AM modulation@1kHz
• 80M-1000MHz: 10V/m
• 1.4G-2.0GHz: 3V/m
• 2.0G-2.7GHz: 1V/m
EN61000-4-4 
Electrical fast 
transient/burst 
immunity *1
Immunity test in 
which burst noise is 
applied to the power 
line and signal line.
• AC/DC main power, I/O power, 
AC I/O (unshielded): 2kV
• DC I/O, analog, communication: 
1kV
EN61000-4-5
Surge immunity *1
Immunity test in 
which lightning 
surge is applied to 
the power line and 
signal line.
• AC power line, AC I/O power, 
AC I/O (unshielded)
: 2kV CM, 1kV DM
• DC power line, DC I/O power
: 0.5kV CM, DM
• DC I/O, AC I/O (shielded), 
analog*2, communication: 1kV 
CM
EN61000-4-6 
Immunity to 
conducted 
disturbances, 
induced by radio-
frequency fields *1
Immunity test in 
which high 
frequency noise is 
applied to the power 
line and signal line.
0.15M-80MHz, 80% AM 
modulation@1kHz, 10Vrms
EN61000-4-8
Power-frequency 
magnetic field 
immunity *1
Immunity test in 
which the product is 
installed in inductive 
magnetic field.
50Hz/60Hz, 30A/m
EN61000-4-11 
Voltage dips and 
interruption 
immunity *1
Immunity test in 
which power supply 
voltage is 
momentarily 
interrupted.
• Apply at 0%, 0.5 cycles and 
zero-cross point
• 0%, 250/300 cycles (50/60Hz)
• 40%, 10/12 cycles (50/60Hz)
• 70%, 25/30 cycles (50/60Hz)