The precautions required when installing a noise filter are described 
below.
(1) Do not bundle the wires on the input side and output side of the 
noise filter. When bundled, the output side noise will be induced 
into the input side wires from which the noise was filtered.
(2) Earth the noise filter earthing terminal to the control cabinet with the 
shortest wire possible (approx. 10 cm (3.94 in.)).
3.1.7 Power line for external power supply terminal
Use a CE-marked AC/DC power supply for an external power supply of 
the modules, and the power cable length needs to be less than 30m 
(98.43 ft.).*1
Install noise filters to external supply power terminals of the I/O module 
and the modules below.
Use noise filters whose damping characteristic is equivalent to that of 
the MA1206 produced by TDK Lambda Corporation.
 • Analog-digital converter module
 • Digital-analog converter module
 • Analog I/O module
 • Temperature input module
 • Temperature control module
 • Pulse input module
 • High-speed counter module
 • Positioning module
(a) The noise will be 
included when the input 
and output wires are 
bundled.
(b) Separate and lay the input 
and output wires.
*1 The power cable length for the A1SJ71E71N-B5 needs to be less 
than 3m (9.84 ft.).
(power supply side)
Input side 
(device side)
Output side 
Filter
(power supply side)
Input side 
(device side)
Output side 
Induction
Filter