110
Table 6.3 Error Code List for A2ASCPU(S1/S30) and A2USHCPU-S1 (Continue)
Error
Massage
Error
Code
(D9008)
Detailed
Error
Code
(D9091)
CPU
States
Error and Cause Corrective Action
"CAN'T
EXECUTE
(P)"
(Checked at
execution of
instruction.)
13
133
STOP
(1) The instruction
was included in the
program and
executed though the
instruction was
not given.
(2) The
instructions were
included in the
program and
executed though the
instruction was
not given.
(3) Nesting level of the
, and
instructions is 6 levels
or deeper, and the 6th
level was executed.
(4) There is no or
instruction at
execution of the
or instruction.
(1) Read the error
step using a
peripheral
device, check
contents and
correct
program of the
step.
(2) Reduce the
number of
nesting levels
of the ,
and
instructions to
5 or less.
134
The instruction was
included in the program
and executed though no
sub program was
provided.
Read the error step
using a peripheral
device and delete
the instruction
circuit block.
135
(1) and
instructions are not
paired.
(2) There are 33 or more
sets of and
instructions.
(1) Read the error
step using a
peripheral
device, check
contents and
correct
program of the
step.
(2) Reduce the
number of sets
of
and
instructions to
32 or less.
RET
CALL
NEXT
LEDA/BBREAK
FOR
CALL CALLP FOR
RET
NEXT
CALL
FOR
CALL
CALLP FOR
CHG
CHG
LEDA/B IX
LEDA/B IXEND
LEDA/B IX
LEDA/B IXEND
LEDA/B IX
LEDA/B IXEND

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi MELSEC-A A1SHCPU and is the answer not in the manual?

Mitsubishi MELSEC-A A1SHCPU Specifications

General IconGeneral
BrandMitsubishi
ModelMELSEC-A A1SHCPU
CategoryController
LanguageEnglish

Related product manuals