Part name FigureCheck method and criterion
Defrost thermistor
(RT61) (MUZ)
Ambient temperature
thermistor (RT65)
Outdoor heat exchanger
temperature thermistor
(RT68)
Normal
1.20k ~ 1.55k
Normal
0.39 ~ 0.49
Discharge temperature
thermistor (RT62)
Fin temperature
thermistor (RT64)
Measure the resistance between terminals using a tester.
(Winding temperature : 14°F ~ 104°F)
Compressor
W
U
V
WHT
RED
BLK
Measure the resistance between lead wires using a tester.
(Part temperature : 14°F ~ 104°F)
Outdoor fan motor
Measure the resistance using a tester. (Part temperature : 14°F ~ 104°F)
R. V. coil
(MUZ)
Measure the resistance using a tester.(Part temperature : 14°F ~ 104°F)
Linear expansion valve
LEV
WHT
RED
YLW
BRN
ORN
BLU
Color of lead wire
Normal
WHT - RED
RED - ORN
YLW - BRN
BRN - BLU
38 ~ 50
MUZ-A24NA MUY-A24NA
U
RED
WHT
BLK
V
W
(W)
(V)
(U)
Normal
RED - BLK
BLK - WHT
WHT - RED
13 ~ 16
Color of lead wire
Measure the resistance with a tester.
Refer to 10-6. “Test point diagram and voltage”,3. “Outdoor electronic
control P.C. board”, the chart of thermistor.
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
Refer to 10-6. “Test point diagram and voltage”,3. “Outdoor electronic
control P.C. board”, the chart of thermistor.
OB451--2.qxp 06.3.29 9:49 AM Page 41