16
MUZ-GE50VA MUZ-GE50VAH
Outdoor
heat
exchanger
Flared connection
Defrost
thermistor
RT61
Discharge
temperature
thermistor
RT62
Flared connection
Stop valve
(with strainar)
Stop valve
(with service port)
Capillary tube
ø
3.6
×
ø
2.4
×
50
Refrigerant flow in cooling
Compressor
4-way valve
Refrigerant flow in heating
Refrigerant pipe
ø
12.7
(with heat insulator)
Refrigerant pipe
ø
6.35
(with heat insulator)
LEV
R.V. coil
heating ON
cooling OFF
Muffler
#100
Receiver
Outdoor heat
exchanger
temperature
thermistor
RT68
Ambient
temperature
thermistor
RT65
Strainer
#100
Unit: mm
ADDITIONAL REFRIGERANT CHARGE (R410A: g)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
5 m 6 m 7 m 8 m 9 m 10 m 11 m 12 m 13 m 14 m 15 m 20 m
MUZ-GE25 800
0 0 0 30 60 90 120 150 180 210 240 390
MUZ-GE35/42 1,150
Calculation: X g = 30 g/m × (Refrigerant piping length (m) - 7)
Model
Outdoor unit
precharged
Refrigerant piping length (one way)
7 m 10 m 15 m 20 m 25 m 30 m
MUZ-GE50 1,550 0 60 160 260 360 460
Calculation: X g = 20 g/m × (Refrigerant piping length (m) – 7)
NOTE: Refrigerant piping exceeding 7 m requires additional refrigerant charge according to the calculation.
Max. Length
A
Max. Height
difference
B
Indoor
unit
Outdoor unit
MAX. REFRIGERANT PIPING LENGTH and MAX. HEIGHT DIFFERENCE
Refrigerant piping: m
Piping size O.D: mm
Max. Length
A
Max. Height difference
B
Gas Liquid
MUZ-GE25/35/42 20 12 9.52
6.35
MUZ-GE50 30 15 12.7