En-3
1-5. INSTALLATION DIAGRAM
Unitsshouldbeinstalledbylicensedcontractoraccordingtolocalcoderequirements.
ACCESSORIES
Checkthefollowingpartsbeforeinstallation.
(1) Drainsocket 1
(2) Draincap 5
PARTS TO BE PROVIDED AT YOUR SITE
(A) Powersupplycord* 1
(B)
Indoor/outdoorunitconnectingwire
* 1
(C) Extensionpipe 1
(D) Wallholecover 1
(E) Pipingtape 1
(F)
Extension drain hose
(orsoftPVChose,15mminner
diameterorhardPVCpipeVP16)
1
(G) Refrigeration oil
Little
amount
(H) Putty 1
(I) Pipexingband 2to7
(J) Fixingscrewfor(I) 2to7
(K) Wallholesleeve 1
(L)
SoftPVChose,15mminner
diameterorhardPVCpipeVP16
fordrainsocket(1)
1
Note:
*Placeindoor/outdoorunitconnecting wire(B)and
powersupplycord(A)atleast1mawayfromthe
TVantennawire.
The“Q’ty”for(B)to(K)intheabovetableisquantity
tobeusedperindoorunit.
Morethan
100mm
Openasarule
Morethan500mm
if the front and both
sidesareopen
Morethan100mm
Morethan200mmifthereare
obstacles to both sides
Openasarule
Morethan500mmiftheback,
bothsidesandtopareopen
Morethan350mm
Outdoor unit installation
Air inlet
Air outlet
Air inlet
950mm
600mm
175
mm
2-U-shapenotchedholes
(BaseboltM10)
330mm
2-12mm×36mm
ovalholes(BaseboltM10)
370mm
417mm
After the leak test, apply insulat-
ing material tightly so that there
isnogap.
Whenthepipingistobeattachedto
awallcontainingmetals(tinplated)
or metal netting, use a chemically
treated wooden piece 20 mm or
thicker between the wall and the
pipingorwrap7to8turnsofinsula-
tionvinyltapearoundthepiping.
To use existing piping, perform
COOL operation for 30 minutes
and pump down before removing
theoldairconditioner.Remakeare
accordingtothedimensionfornew
refrigerant.
1-6. DRAIN PIPING FOR OUTDOOR UNIT
1) Performthedrainpipingworkonlywhendrainingfromoneplace.
2) Providedrainpipingbeforeindoorandoutdoorpipingconnection.
3) Attachthedrainsockettooneoftheseveraldrainholes.
Fixthedrainsocketintothedrainholeofthebaseusingthecatchestosecureit
inplace.
4) ConnectthesoftPVChoseI.D.15mmasshownintheillustration.
5) Makesuretoprovidedrainpipingwithadownhillgradeforeasydrainow.
6) Gluethedraincapstoclosealltheotherunnecessaryholeswiththeglue(Prepare
intheeld).
Note:
Applythegluesecurely,astheglue(Prepareintheeld)willworkassealtoprevent
waterfromleaking.
Usetheadhesivefortherubberandmetal.
Attention
Theoutdoorunitisprovidedwithseveralholesfordrainageatthebottomtomake
drainage easier.
Thedrainsocketisusedtoclosetheunnecessaryholesandcentralizethedrainage
whenusingthedraintubeattheinstallationplace.
Donottousethedrainsocketincoldregion.Thedraintubecanbefrozen.
(1)Drainsocket
(2)Draincap
(L)SoftPVChose
IMPORTANT NOTES
TocomplywiththerequirementsofAustralianstandardAS/NZS3000electricalinstallations
(wiring rules), the electrical wiring required between the indoor and outdoor units must be
installed by a licenced electrical contractor.