36
<DRY operation time chart>
Minimum 3 minutes w1
ON
Thermostat
Indoor fan
Auto vane
Drain pump
Booster heater
Compressor
ON
ON
DRY MODE
DRY MODE
ON
ON
OFF
OFF
ON
OFF
3 minutes
OFF
OFF
OFF
OFF
Operation starts by
POWER button
ON.
Operation stops by
POWER button
OFF.
Room temperature
becomes equal to
set temperature.
Room temperature
rises above set
temperature.
w1 Even if the room temperature rises above the set temperature during this period, the compressor will not start until
this period has ended.
2-2 DRY operation
(1) Compressor control
13-minute time delay
To prevent overload, the compressor will not start within 3 minutes after stop.
2The compressor stops in check mode or during protective functions.
<How to operate>
1 Press POWER ON/OFF button.
2 Press the button to display “
3 Press the TEMP. button to set the desired temperature.
NOTE: The set temperature changes 1°C when the or
button is pressed one time.
Dry 19 to 30°C
FILTER
CHECK MODE
TEST RUN
ON/OFF
CHECK
ADDRESS
UNIT No.
FUNCTION No.
SELECTION No.
AM
PM
AM
PM
TEST RUN
FUNCTION
˚C
TEMP.
WIRED REMOTE
CONTROLLER
WIRELESS REMOTE
CONTROLLER
PLH-3AK.UK
PLH-3AKH.UK
PLH-4, 5, 6AKS.UK
PLH-4, 5, 6AKHS.UK
PLH-3AK1.UK
PLH-3AKH1.UK
PLH-4, 5, 6AKS1.UK
PLH-4, 5, 6AKHS1.UK
OC211-A--2.qxp 04.9.28 4:41 PM Page 36