57
PLH-3AK1.UK PLH-4, 5, 6AKS1.UK
PLH-3AKH1.UK PLH-4, 5, 6AKHS1.UK
ON/OFF
TEMP
FAN
VANE
MODE
CHECK
LOUVER
TEST RUN
AUTO STOP
AUTO START
h
min
RESET
SET
CLOCK
4
3
2
1 Turn on the main power to the unit.
2 Press the button twice continuously.
• begins to light and refrigerant address display “00” begins to bink.
• Start this operation from the status of remote controller display turned off
3 While pointing the remot controller toward the unit’s receiver, press the
button
• If the buzzer sounfd is heard and the ON/OFF lamp (unit display) blinks,
refer to following table.
4 While pointing the remote controller toward the unit’s receiver, press the
ON/OFF button.
• Self-check mode is canceled.
Check Code
1
2
3
4
5
6
7
8
9
Suction sensor alarm
Plpe sensor alarm
Transmission alarm
Drain sensor alarm
Drain pump alarm
Anti-freezing on
Anti-overheat on
System error
Outdoor unit alarm
No alarm (no error)
Single beep ✕ 1
Single beep ✕ 2
Single beep ✕ 3
Single beep ✕ 4
Single beep ✕ 5
Single beep ✕ 6
Single beep ✕ 6
Single beep ✕ 7
Single beep ✕ 8
Receiving signal only
(no error alarm)
Alarm Buzzer sound
(WIRELESS REMOTE CONTROLLER)
OC211-A--2.qxp 04.9.28 4:41 PM Page 57