EasyManuals Logo

Mitsubishi Q64TD User Manual

Mitsubishi Q64TD
18 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
4
*2: A period until a thermocouple input value/micro voltage input value is converted
into a temperature
measurement value/micro voltage conversion value.
*3: A period until a thermocouple input value/micro voltage input value is converted into a
temperature measurement value/micro voltage conversion value and the resultant value is stored
into the buffer memory.
The conversion speed is a delay time that occurs during sampling processing. It is independent of
averaging processing.
Example: When two channels are enabled for conversion
(Conversion speed) = (sampling period)
3
= (20ms
2 channels) 3
= 120ms
CH.1 CH.2
Input 1)
Conversion speed
Conversion processing
Buffer memory
Input 2)
CH.1 CH.2
CH.1 CH.2 CH.1 CH.2 CH.1 CH.2
Input 1)
Input 2)
Conversion speed
*4:At wire break detection, the temperature measurement value/micro voltage conversion value right
before wire break occurrence is held.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi Q64TD and is the answer not in the manual?

Mitsubishi Q64TD Specifications

General IconGeneral
BrandMitsubishi
ModelQ64TD
CategoryController
LanguageEnglish

Related product manuals