5   DATA USED FOR POSITIONING CONTROL 
 
 
 
Item Setting details 
Setting value
1  
00: Not used 
01: 1125
Hz
 
02: 563
Hz
 
03: 375
Hz
 
04: 282
Hz
 
05: 225
Hz
 
06: 188
Hz
 
07: 161
Hz
 
 
00: Invalid          08: 141[Hz] 
01: 1125[Hz]      09: 125[Hz] 
02: 563[Hz]        10: 113[Hz] 
03: 375[Hz]        11: 102[Hz] 
04: 282[Hz]        12: 94[Hz] 
05: 563[Hz]        13: 87[Hz] 
06: 375[Hz]        14: 80[Hz] 
07: 282[Hz]        15: 75[Hz] 
 
00: Invalid          10: 281.3[Hz] 
01: 4500[Hz]      11: 264.7[Hz] 
02: 2250[Hz]      12: 250[Hz] 
03: 1500[Hz]      13: 236.8[Hz] 
04: 1125[Hz]      14: 225[Hz] 
05: 900[Hz]        15: 214.3[Hz] 
06: 750[Hz]        16: 204.5[Hz] 
07: 642.9[Hz]     17: 195.7[Hz] 
08: 562.5[Hz]     18: 187.5[Hz] 
09: 500[Hz]        19: 180[Hz] 
0A: 450[Hz]        1A: 173.1[Hz] 
0B: 409.1[Hz]     1B: 166.7[Hz] 
0C: 375[Hz]        1C: 160.1[Hz] 
0D: 346.2[Hz]     1D: 155.2[Hz] 
0E: 321.4[Hz]     1E: 150[Hz] 
Notch filter selection 
0F: 300[Hz]         1F: 145.2[Hz] 
 
Pr.118
 
Machine resonance suppression filter 
Notch depth selection 
Used to set the notch frequency to match the 
response frequency of the mechanical system. 
0: Deep     (-40db) 
1: 
          (-14db) 
2: 
          (-8db) 
3: Shallow (-4db) 
 
Servo adjustment parameters 
Pr.119
 
Feed forward gain 
Used to set the feed forward gain for position control. 
Set "100" to nearly zero the droop pulse value when 
operation is performed at constant speed. 
Note that sudden acceleration/deceleration will 
increase overshoot. 
POINT
 
 Be sure to set up this parameter "2: Invalid (No auto  
 tuning) when you set up 
Pr.108
 
Auto tuning. 
0 to 100[%]