253
-
'16 • SCM-T-199
E10
Excessive number of connected
indoor units (more than 17 units)
by controlling with one remoto control
Keeps ashing
Stays OFF
Outdoor
–
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis Countermeasure
Aren't more than 17
indoor units connected to one
remote control?
NO
YES
Defective remote control
→
Replace.
Reduce to 16 or less units.
2. Error detection method
When it detects more than 17 of
indoor units connected to one
remote contorl
3 .
Condition of error displayed
Same as above
4. Presumable cause
• Excessive number of indoor
units connected
• Defective remote control
Note:
Error code
Remote control:
LED Green Red
Indoor
Content