EasyManua.ls Logo

Mitsubishi SRC92ZL-S

Mitsubishi SRC92ZL-S
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
-
18
-
'12 • SRK-T-130
7. CAPACITY TABLE
ISC12091
Model
SRK92ZL-S Cool Mode
Heat Mode(HC)
Air flow
Outdoor
air temp.
Indoor air temp
21
DB 23
DB 26
DB 27
DB 28
DB 31
DB 33
DB
14
WB 16
WB 18
WB 19
WB 20
WB 22
WB 24
WB
TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC TC SHC
Hi
21.0
(m
3
/min)
10
10.37
7.61
10.85
7.48
11.25
7.67
11.44
7.56
11.64
7.44
11.98
7.58
12.30
7.31
12
10.18
7.51
10.67
7.38
11.09
7.59
11.29
7.48
11.49
7.38
11.85
7.52
12.18
7.27
14 9.99 7.40
10.48
7.28
10.93
7.51
11.13
7.41
11.34
7.31
11.72
7.47
12.06
7.23
16 9.79 7.28
10.29
7.19
10.76
7.43
10.98
7.34
11.18
7.25
11.58
7.41
11.93
7.18
18 9.59 7.18
10.09
7.07
10.58
7.34
10.81
7.26
11.02
7.17
11.43
7.36
11.79
7.13
20 9.38 7.06 9.88 6.98
10.40
7.26
10.64
7.19
10.85
7.09
11.28
7.29
11.65
7.07
22 9.16 6.96 9.67 6.87
10.21
7.17
10.47
7.11
10.68
7.00
11.13
7.24
11.50
7.02
24 8.94 6.84 9.45 6.77
10.02
7.07
10.29
7.01
10.50
6.93
10.97
7.17
11.35
6.97
26 8.72 6.72 9.22 6.65 9.82 6.98
10.10
6.94
10.32
6.86
10.80
7.11
11.19
6.89
28 8.49 6.59 8.99 6.54 9.62 6.90 9.91 6.86
10.13
6.78
10.63
7.01
11.03
6.83
30 8.25 6.48 8.76 6.42 9.41 6.80 9.71 6.78 9.93 6.71
10.45
6.95
10.86
6.78
32 8.01 6.35 8.51 6.31 9.20 6.71 9.51 6.69 9.73 6.62
10.27
6.88
10.68
6.72
34 7.77 6.23 8.27 6.19 8.98 6.61 9.31 6.59 9.52 6.53
10.08
6.82
10.50
6.66
35 7.64 6.17 8.14 6.13 8.86 6.56 9.20 6.55 9.42 6.49 9.99 6.78
10.41
6.63
36 7.51 6.11 8.01 6.07 8.75 6.50 9.09 6.51 9.31 6.45 9.89 6.75
10.32
6.60
38 7.26 5.97 7.75 5.94 8.52 6.41 8.88 6.41 9.09 6.35 9.69 6.68
10.12
6.53
39 7.12 5.91 7.62 5.88 8.40 6.35 8.77 6.37 8.98 6.31 9.59 6.63
10.03
6.50
(
kW
)
Air flow
Outdoor
air temp.
Indoor air temp
16
DB 18
DB 20
DB 22
DB 24
DB
Hi
23.5
(m
3
/min)
-15
WB 6.15 6.02 5.88 5.76 5.63
-10
WB 6.96 6.84 6.75 6.58 6.44
-5
WB 7.54 7.43 7.28 7.20 7.08
0
WB 7.91 7.79 7.65 7.56 7.45
5
WB 10.07 9.95 9.90 9.70 9.57
6
WB 10.23 10.11 10.00 9.87 9.75
10
WB 10.87 10.77 10.70 10.56 10.45
15
WB 11.84 11.73 11.65 11.52 11.41
20
WB 12.72 12.62 12.56 12.41 12.31
Note (1) These data show average statuses.
Depending on the system control, there may be ranges where the operation is not conducted continuously.
These data show the case where the operation frequency of a compressor is xed.
(2) Capacities are based on the following conditions.
Corresponding refrigerant piping length : 7m.
Level difference of Zero.
(3) Symbols are as follows.
TC:Total cooling capatity
SHC:Sensible heat capacity
HC:Heating capacity
(
kW
)

Related product manuals