Monitor the time.
Monitor the year/month/day of the PC and connected G-50A.
[Procedure]
1) Select [Time set-up] button.
Click the [Time set-up] button located in the system
setting group on the initial window.
2) Select [Time monitor].
Click the [Time monitor] button on the time set-up select
screen.
3) Select the [Monitor] button.
In this case, click the [Monitor] button on the time monitor
screen. When the button is clicked, the differ- ence
between the date/time of all G-50A units connected to
the PC (personal computer) on which the integrated
centralized control software TG-2000A operates and the
reference machine is displayed.
* There is a difference of several seconds depending
on the monitor timing.
4) Select [OK] button.
When the time confirmation is completed, click the [OK] button, and the initial screen returns.
Note:
• Don’t change time in the following cases. However, this only applies when the charge function is on.
Because charge collection processing is performed.
When the current time is between 04:00 and 07:00.
• We recommend that the time be checked and corrected once a month.
Execute the correction of time within time of 08:00 to 21:45.When the RS-485 WHM
however, do not correct the time near the charge zone change time.
• The date display order depends on the OS setting.
• When the date is exceeded after the start of operation and the time is reset, air-