EasyManua.ls Logo

Mod Con 300 - Diagrams for Sidewall Venting

Mod Con 300
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
GAS-FIRED BOILER Boiler Manual
I. DIAGRAMS FOR SIDEWALL VENTING
GENERAL NOTE: All vent pipes must be glued, properly supported and the exhaust must be pitched a
minimum of a ¼" per foot back to the heater (to allow drainage of condensate).
0,1
0,1
327(17,$/612:/(9(/
25
$%29(0$;
5,*+76,'(9,(:
(;+$867
9(17
$,5,17$.(
9(17
6833257%5$&.(76
0867%(86('21
$//+25,=217$/
$1'9(57,&$/3,3,1*
7((
675$,*+7
&283/,1*
7239,(:
0$;
(;+$867
9(17
$,5,17$.(
9(17
7((
675$,*+7
&283/,1*
127(9(170867%($7/($6729(50$;,080612:
/(9(/25:+,&+(9(5,6*5($7(5&+(&.:,7+/2&$/
&2'(5(48,5(0(176
NOTE: When placing support brackets on vent piping, the first bracket must be within 1 foot of the
appliance and the balance at 4 foot invervals on the vent pipe. The boiler venting must be readily
accessible for visual inspection for the first three feet from the boiler.
Figure 6-9
LP-205-E Rev. 5/15/08 Figure 6-10 LP-205-F Rev. 5/15/08
SIDEWALL VENTING W/TEE (INTAKE)
AND COUPLING (EXHAUST)
327(17,$/612:/(9(
/
25
$%29(0$;
5,*+76,'(9,(:
6833257%5$&.(76
0867%(86('21
$//+25,=217$/
$1'9(57,&$/3,3,1*
(;+$867
9(17
,17$.($,5
9(17
9(17.,7
6((&+$57
127(9(170867%($7/($6729(50$;,080612:
/(9(/25:+,&+(9(5,6*5($7(5&+(&.:,7+/2&$/
&2'(5(48,5(0(176
SIDEWALL VENTING WITH KIT
PART 6: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL (CONTINUED)

Table of Contents