1MCP15-500.9
October, 2020
INSTALLATION AND SERVICE MANUAL
commercial packaged ventilation system units
model MPR (for units with 24 digit model numbers)
MCP15-500.9
5H0816400000
Inspection on Arrival
1. Inspect unit upon arrival. In case of damage, report it
immediately to transportation company and your local
factory sales representative.
2.
Check rating plate on unit to verify that power supply meets
available electric power at the point of installation.
3. Inspect unit upon arrival for conformance with description
of product ordered (including specifications where
applicable).
THIS MANUAL IS THE PROPERTY OF THE OWNER.
PLEASE BE SURE TO LEAVE IT WITH THE OWNER WHEN YOU LEAVE THE JOB.
Improper installation, adjustment, alteration,
service or maintenance can cause property
damage, injury or death, and could cause
exposure to substances which have been
determined by various state agencies to cause
cancer, birth defects or other reproductive
harm. Read the installation, operating and
maintenance instructions thoroughly before
installing or servicing this equipment.
WARNING
This unit contains R-410A high pressure
refrigerant. Hazards exist that could result in
personal injury or death. Installation,
maintenance, and service must only be
performed by an HVAC technician qualified in
R-410A refrigerant and using proper tools and
equipment. Due to much higher pressure of
R-410A refrigerant, DO NOT USE service
equipment or tools designed for refrigerants
other than R410A.
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could
result in serious injury, death or property
damage.
Be sure to read and understand the installation,
operation and service instructions in this manual.
Improper installation, adjustment, alteration,
service or maintenance can cause serious
injury, death or property damage.
Do not store or use gasoline or other
flammable vapors and liquids in the vicinity
of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS:
• Do not try to light any appliance.
Do not touch any electrical switch, do
not use any phone in your building.
• Leave the building immediately.
Immediately call your gas supplier from
a phone remote from the building.
Follow the gas suppliers instructions.
If you cannot reach your gas supplier,
call the fire department.
Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
WARNING

Questions and Answers

  • S
    Susan BergerAug 14, 2025
    How to troubleshoot a power failure in my Modine Manufacturing Fan?
    • J
      jeremiah94Aug 14, 2025
      If your Modine Manufacturing Fan has a power failure, there are several potential causes: * The disconnect switch may not be turned on. If so, turn it on. * Fuses might be blown, or the circuit breaker could be open. In this case, check and replace the fuses or reset the circuit breaker. * The main power supply to the unit may be off. Turn the power on at the main panel.
  • A
    ariastroyAug 17, 2025
    What to do if my Modine Manufacturing MPR15 motor fails?
    • S
      stevengillAug 17, 2025
      If the motor of your Modine Manufacturing Fan fails, possible causes include a failed motor (check and replace it), loose wiring to the motor (check and tighten), motor overload (reset the motor starter and check the motor load), or improper supply voltage (check and correct).
  • M
    Melanie CollinsAug 20, 2025
    Why is the blower on my Modine Manufacturing Fan not turning or turning slowly?
    • M
      Maria LewisAug 20, 2025
      If the blower in your Modine Manufacturing Fan isn't turning or is turning slowly, consider these potential causes: * A broken drive belt (check and replace it). * Motor voltage too low (check and correct). * Supply power line sizing too small (check and correct). * Controls are in Unoccupied mode (wait for Occupied mode or override). * Controller alarm (check and correct). * Blower door open (close the door).
  • J
    Jason RodriguezAug 25, 2025
    How to fix insufficient airflow in my Modine Manufacturing MPR15 Fan?
    • D
      Dana HallAug 25, 2025
      If your Modine Manufacturing Fan has insufficient airflow, several factors could be responsible: * The motor may be running backwards; check and correct the motor wiring to the phase rotation of the supply power, reversing any two lines to the motor. * The fan speed setting might be too low; check and correct it. * Filters or coils could be dirty or clogged; check and clean or replace them. * The duct system may have more static pressure drop than expected; check and correct it. * Dampers and/or discharge registers may be closed; check and correct.
  • T
    Todd MartinezAug 28, 2025
    What causes excessive airflow in my Modine Manufacturing MPR15 Fan and how can I resolve it?
    • A
      Amy LewisAug 28, 2025
      If your Modine Manufacturing Fan has excessive airflow, consider these possible causes: * The fan speed setting is too high. Check and correct it. * Filters are not in place. Check and reinstall them. * Ductwork grilles or registers are not installed. Check and install them. * The duct system has less static pressure drop than expected. Check and correct it. * An access door is open. Close all unit side access doors.
  • W
    William FloresAug 31, 2025
    Why won't the compressor(s) in my Modine Manufacturing MPR15 Fan operate?
    • M
      millertaraAug 31, 2025
      If the compressor(s) in your Modine Manufacturing Fan do not operate, here are some things to check: * The controls may be in Unoccupied mode. Wait for Occupied mode or override. * There may be an ambient lockout, low pressure lockout, or high pressure lockout. Check and wait or override. * There might be an inter-stage delay. Check and wait or override. * The airflow proving switch may not be closing. Check and correct it. * The thermostat may not be calling for cooling. Check and wait or override. * The drain pan float switch may be open. Check the switch and the drain line (pan, trap, piping) for proper drainage, and verify the trap is primed with water.
  • C
    Cory WilliamsonSep 3, 2025
    What could be wrong if the gas heat isn't functioning properly in my Modine Manufacturing MPR15 Fan?
    • S
      Sharon OconnorSep 3, 2025
      If the gas heat in your Modine Manufacturing Fan is not functioning properly, consider the following: * The thermostat may not be calling for heat. Check and wait or override. * Limit switches may be open. Check and correct. * The main gas supply may not be turned on. Check and correct. * There may be air in the gas line. Purge per instructions. * Loose wiring to ignition controls or gas valves. Check and tighten. * A failed ignition controller or gas valve. Check and replace. * A failed flame sensor. Check and replace. * Improper supply air temperature sensor installation. Check and correct. * Clogged condensate drain line (condensing or hybrid condensing heat option only). Check condensate drain line, clear as needed.
  • T
    Tammy MartinezSep 6, 2025
    What should I do if the dampers on my Modine Manufacturing Fan aren't working?
    • Z
      zhernandezSep 6, 2025
      If the dampers in your Modine Manufacturing Fan do not operate, possible causes include: * Failed damper motor(s). Check and replace. * Loose wiring to damper motor(s). Check and tighten. * Controls are in Unoccupied mode. Wait for Occupied mode or override. * Ambient lockout. Check and wait or override.
  • J
    Jessica FrenchSep 10, 2025
    Why is the electric heat not functioning in my Modine Manufacturing MPR15 Fan?
    • K
      Kelly OlsonSep 10, 2025
      If the electric heat in your Modine Manufacturing Fan is not functioning, check for these potential issues: * Thermostat not calling for heat: Check and wait or override. * Limit switches are open: Check and correct. * Overload relay is tripped: Check and correct. * Failed heat modules: Check and replace.

Summary

Special Precautions

Installation Guidelines

Condensate Drain Installation

Electrical Connections

Electrical Connection Procedures

Detailed instructions for making electrical connections, including wiring diagrams and sizing.

Gas Connections

Gas Connection Procedures

Guidelines for connecting the gas supply, including pressure testing and piping requirements.

Furnace Condensate Drain;Trap Installation

Start-Up Procedure

General Start-Up Checks

Initial steps before starting the unit, including power disconnect and door checks.

Blower Adjustments

Procedures for adjusting blower speed for optimal airflow and performance.

Checking Refrigerant Charge

Procedure for verifying and adjusting the refrigerant charge using superheat and subcooling.

Gas Heating Option Start-Up

Steps for starting up the gas heating system, including pressure checks and adjustments.