SECTION
FOUR
MAINTENANCE
4.1
SCHEDULED PREVENTIVE MAINTENANCE
To guarantee the entire fire alarm system is operating properly, it is
recommended a test (Alarm and Trouble condition) be performed once each
month. Tests shall be made under direct supervision of the owner or a
qualified person representing the owner and the municiple authorities
having jurisdiction.
A complete record shall be kept of all tests and operation of the system
(inspection of all equipment condition, both visual and functional,
including all batteries). After each test, the system shall be restored to
the Normal condition.
Occupants of the building shall be notified in advance as to time of
testing of sounding devices. Such tests should be held during daytime
hours.
4.2 DISASSEMBLY
AND
REASSEMBLY
Remove all
AC
input power and battery backup power from the Control Panel
enclosure before attempting to replace any components. Refer to wiring
diagrams and schematics in the Appendix for actual wiring configuration.
4.2.1
Control Panel
The Control Panel is located in the upper portion of the enclosure. Dis-
assembly requires the following:
o Remove the AC protective shield located on the top left corner of
the assembly.
o
Remove the three AC input wires
attached to terminal block (TB1).
555
P
DOCUMENT
NO.
001-097-00
PAGE
4-1