6 REV-02 100418
Full Parameter List
Parameter
Description
Adjustment Range
Factory Setting
F001
Motor FLA
50-100% of Max Amp Rating (less Service Factor)
0
F002
Motor Service Factor
1.00-1.30
1.00
F003
Overload Class During Start
NEMA/UL Class 5-30
10
F004
Overload Class During Run
NEMA/UL Class 5-30
10
F005
Overload Reset
0=Manual, 1=Auto, 2=Disabled
0:Manual
F10
Ramp Type (If Ramp 2 is not being used, unit
will ignore all settings referenced to Ramp 2)
Ramp #1 Ramp #2
1
Setting = 1
Setting = 2
Setting = 3
Setting = 4
Voltage Voltage
Current Current
Voltage Current
Current Voltage
F011
Initial Voltage of Ramp 1
0-100% Line Voltage
60%
F012
Initial Current of Ramp 1
0-600% Motor Current
200%
F013
Accel Ramp Time of Ramp 1
1-120 seconds
10 sec
F014
Max Current Limit of Ramp 1
200 - 600% Motor Current
350%
F015
Initial Voltage of Ramp 2 (if Ramp 2 is used)
0-100% Line Voltage
60%
F016
Initial Current of Ramp 2 (if Ramp 2 is used)
0-600% Motor Current
200%
F017
Accel Ramp Time of Ramp 2 (if Ramp 2 is used)
1-120 seconds
10Sec.
F018
Max Current Limit of Ramp 2 (if Ramp 2 is used)
200 - 600% Motor Current
350%
F019
Voltage Jog
5-100% Line Voltage
50%
F020
Time of Voltage Jog
1-20 seconds
10 sec
F021
Current Jog
100-500% Motor Current
150%
F022
Kick Start Voltage
0=Disabled or 10-100% Line Voltage
0
F023
Kick Time
0.1-2 seconds
0.8 sec
F024
Deceleration Ramp (Pump Control)
0=Disabled (Coast to Stop)
1=Enabled (except after OL trip)
2=Enabled (Deceleration even during O/L trip)
0
F025
Begin Decel Level (BDL)
0 - 100 % of Output Voltage
60%
F026
Decel Shut Off Voltage
0 to (BDL minus 1)% Voltage
30%
F027
Decel Ramp Time
1-60 seconds
10Sec.
F028
Auto Restart Delay Time
0=Disabled or 1-999sec after Power Loss
0
F029
Voltage Input
200 - 690 Volt
480
F030
Voltage Imbalance Trip %
0, 1 - 30% [0=Disabled]
0
F031
Voltage Imbalance Trip Delay
1 - 20 seconds
10
F032
Over Voltage Trip %
0, 1 - 10% [0=Disabled]
0
F033
Over Voltage Trip Delay
1 - 20 seconds
10
F034
Under Voltage Trip on Start %
0, 1 - 20% [0=Disabled]
0
F035
UV Trip on Start Delay
1 - 180 seconds
10
F036
Under Voltage Trip on Run %
0, 1 - 20% [0=Disabled]
0
F037
UV Trip Delay during Run
1 - 20 seconds
2
F038
Shorted SCR and Trip Delay
0, 1-10 seconds [0=Disabled]
1Sec
F039
Shunt Trip Delay
0, 1-10 seconds [0=Disabled]
1Sec
F040
Current Imbalance Trip %
0=Disabled or 5-30% imbalance
0
F041
Current Imbalance Trip Delay
1-20 seconds
2 sec
F042
Over Current Trip %
0=Disabled or 100-300% of Motor FLA
0
F043
Over Current Trip Delay
1-20 seconds
1 sec
F044
Under Current %
0=Disabled or 10-90% of Motor FLA
0
F045
Under Current Trip Delay
1-60 seconds
2 sec
F046
Ground Fault Current Trip Value
0=Disabled or 5-90% of CT ratio from Fn74
0
F047
Ground Fault Current Trip Delay
1-60 seconds
2 sec
F048
Coast Down Lockout Time
0=Disabled or 1-60 minutes
0
F049
Maximum Starts per Hour
0=Disabled or 1-10 Starts
0
F050
Minimum Time Between Starts
0=Disabled or 1-60 minutes
0
F051
nCP Trip (No Control Power)
0, 1 [0=Disabled, 1=Enabled]
1