6 REV-02 100418
50-100% of Max Amp Rating (less Service Factor)
Overload Class During Start
Overload Class During Run
0=Manual, 1=Auto, 2=Disabled
Ramp Type (If Ramp 2 is not being used, unit
will ignore all settings referenced to Ramp 2)
Setting = 1
Setting = 2
Setting = 3
Setting = 4
Voltage Voltage
Current Current
Voltage Current
Current Voltage
Initial Voltage of Ramp 1
Initial Current of Ramp 1
Accel Ramp Time of Ramp 1
Max Current Limit of Ramp 1
Initial Voltage of Ramp 2 (if Ramp 2 is used)
Initial Current of Ramp 2 (if Ramp 2 is used)
Accel Ramp Time of Ramp 2 (if Ramp 2 is used)
Max Current Limit of Ramp 2 (if Ramp 2 is used)
0=Disabled or 10-100% Line Voltage
Deceleration Ramp (Pump Control)
0=Disabled (Coast to Stop)
1=Enabled (except after OL trip)
2=Enabled (Deceleration even during O/L trip)
0 - 100 % of Output Voltage
0 to (BDL minus 1)% Voltage
0=Disabled or 1-999sec after Power Loss
Voltage Imbalance Trip Delay
Under Voltage Trip on Start %
Under Voltage Trip on Run %
Shorted SCR and Trip Delay
0, 1-10 seconds [0=Disabled]
0, 1-10 seconds [0=Disabled]
0=Disabled or 5-30% imbalance
Current Imbalance Trip Delay
0=Disabled or 100-300% of Motor FLA
0=Disabled or 10-90% of Motor FLA
Ground Fault Current Trip Value
0=Disabled or 5-90% of CT ratio from Fn74
Ground Fault Current Trip Delay
0=Disabled or 1-60 minutes
0=Disabled or 1-10 Starts
Minimum Time Between Starts
0=Disabled or 1-60 minutes
nCP Trip (No Control Power)
0, 1 [0=Disabled, 1=Enabled]