1 REV-02 100418
Manual Addendum for VMX-B Configured Soft Start Packages
For use with wiring diagram # 93-3880 Rev B (CB/FS), or 93-3881 Rev B (MLO), and VMX2 user manual.
Introduction: The VMX-B is a configured enclosed soft start, available as a Combination (with C/B or
Fused disconnect) package, or as an MLO (Main Lug Only) package, intended for use in Industrial,
Commercial, Agricultural, or Infrastructure applications.
Line Voltage:
By default units are set-up for 460VAC line power, but can be adjusted to operate on 230VAC or
208VAC at the reduced HP rating. To adjust the operating voltage simply move wire #1L2B from the
480V (H4) terminal to the 230V (H3) or 208V (H2) terminal.
Power Connections:
Line Power input is connected directly to the bottom terminals of the Circuit Breaker, or line terminals
on MLO (Main Lug Only) units, and the motor is connected to the lugs at the bottom of the VMX2 soft
start.
Remote Start / Stop Control connections:
The VMX-B is set up for 2 or 3 wire remote control using dry contacts rated at 120VAC (0.1Amp).
Remote Two Wire Control:
Connect a dry (voltage free) maintained contact closure between terminals 1 and 3 of the customer
terminal strip as shown here.
1 2 3 4 5 6 7 8 9
RUN
Customer Terminals TBC on TCB3000 PCB
Remote Three Wire Control:
For standard 3-wire control, connect dry (voltage free) contacts for the Stop / Start buttons as shown
below of the customer terminal strip. Connect the normally closed “STOP” pushbutton across terminals
1 & 2, and the normally open “START” pushbutton across terminals 2 & 3 of the customer terminal
strip. Note: the unit can be operated in the “Local” position without any external control.
1 2 3 4 5 6 7 8 9
STOP
START
Customer Terminals TBC on TCB3000 PCB
See page 3.
TCB3000 Terminal Control Board
See page 3.
TCB3000 Terminal Control Board
Question and Answer IconNeed help?

Do you have a question about the motortronics VMX-B Soft Start Packages and is the answer not in the manual?

motortronics VMX-B Soft Start Packages Specifications

General IconGeneral
Brandmotortronics
ModelVMX-B Soft Start Packages
CategoryController
LanguageEnglish

Summary

VMX-B Soft Start Package Introduction

VMX-B Overview and Applications

Describes the VMX-B soft start, its packages, and applications.

Line Voltage Adjustment

Details how to adjust the VMX-B for different line voltages (230/208VAC).

Power Connection Details

Explains how line power input connects to the soft start unit.

Remote Start/Stop Control Configuration

Two-Wire Remote Control

Connects dry maintained contact for RUN command.

Three-Wire Remote Control

Uses dry contacts for STOP/START pushbuttons.

Run Status and Auxiliary Contacts

Run Status Output Contacts

Contacts indicating successful RUN command in SOFT or X-LINE mode.

VMX2 Auxiliary Contacts

Programmable auxiliary contacts on TB2 of the VMX2 soft start.

Overload Relay and X-LINE Operation

Overload Relay Operation

Explains setting the overload relay based on motor FLA and CT rating.

X-LINE Mode Functionality

Details full voltage operation via bypass contactor for emergency use.

TCB3000 Terminal Board Customer Connections

Status Indicator LEDs

Explains the function of Green, Yellow, and Red LEDs on the terminal board.

VMX-B Programming Instructions

Entering Motor FLA and Service Factor

Guide to inputting Motor Full Load Amps (FLA) and Service Factor (SF) parameters.

Operation and Troubleshooting

Keypad Operation Modes

Details display and fault modes, including fault codes and their meanings.

Full Parameter List

VMX-B Door Mounted Operators

Command Center Components

Describes the functions of the E-Stop, Start/Stop buttons, selector, and indicator lights.

Wiring Diagram # 93-3980

Wiring Diagram # 93-3981