65
MCTC manual
MCHybrid
For the location of the output connections, see Electrical connections
Mixer valve (OUT-10)
Connection 25 and 26.
In case a MCHybrid is used OFFLINE, on top of a storage bin. It is required to use a material valve underneath
the MCHybrid to guarantee a right mixture. This valve can be connected to this output. See MCHybrid
configuration for enabling this function.
Mixer full and mixing finished: this output is on (24V).
Alarm / Warning Output (OUT-13): Connection 29 and 30.
Warning event: this output is on (24V), the system continues running.
Soft Alarm event: this output is on (24V), the MCHybrid system is in PAUSE.
Alarm event: this output is on (24V), the system stops running.
Free programmable events can be programmed to an Alarm, SoftAlarm or Warning. See chapter: Events -
Configuration for configuring events. For alarm light connection in multicomponent systems see chapter:
Multicomponent Alarm/warning output.
Alarm Output (OUT-13)
Normally open contact, connection 34 and 35
Alarm event: this output is activated, the systems stops running.
Run Output (OUT-14)
Normally open contact, connection 36 and 37
The “RUN signal” can be used as a Start/Stop condition for the molding machine.
For example: Molding machine can only start in case dosing unit is also started.
Default the Run output 2 (OUT-2) is always on in production mode (status Running or Ready)
Production status = STANDBY or DOSING output 36 and 37 are CLOSED.
Production status = OFF output 36 and 37 are OPEN.
In case of alarm, the alarm output (OUT-13) is switched (on) and the system is stopped. This also switches output OUT-14 (off).