Troubleshooting 45
8.12 EH 02 (Zero crossing detection error diagnosis and solution)
Description: When PCB does not receive zero crossing signal feedback for 4 minutes or the zero crossing signal time
interval is abnormal.
Recommended parts to prepare:
Connection wires
Indoor main PCB
Troubleshooting and repair:
Check the connections and
power supply.
Correct the connections. Turn on the
unit when the power supply is good.
NO
Indoor main PCB is defective. Replace
indoor main PCB.