Troubleshooting 49
8.15 (IDU)PC 03/(ODU)PC 31 (Low pressure protection diagnosis and solution)
Description: Outdoor pressure switch cut off the system because low pressure is lower than 0.13 MPa, the LED displays
the failure code.
Recommended parts to prepare:
Connection wires
Outdoor PCB
Low pressure protector
Refrigerant
Troubleshooting and repair: