3103-1001 Rev. 0
once acknowledged, another condition will not reactivate the output.
2. Thirty minutes has elapsed since the User Configured Output was acknowledged by the
operator and the conditions that caused that event are still present.
This operation is in contrast to the Common Alarms, where each new condition causes a reactivation
of the warning or alarm.
A Warning or Alarm indication by the MultiGard 5000 Gas Sampling System requires
immediate action by the operator. Failure to do so may lead to serious injury or death. Once
an operator has acknowledge a User Configured Output, It is imperative that immediate
action be taken to determine the source of this condition, take remedial action and continue to
monitor the Gas Level Screens until all levels return to normal.
NOTE: Unless specifically requested otherwise, the MultiGard 5000 unit is shipped without defining
the functions of the User Configured Outputs. Under those conditions, none of the outputs will
activate until they are configured in the field.